Setting groups
Figure 3.21
Setting Groups menu displays all the information related to group changing.
•
Active setting group
displays the current active setting group 1…8.
•
It is possible to activate desired setting group by setting
Force SG
. While doing this Force SG change has to be enabled.
•
In
Used setting groups
menus it is possible to activate setting groups between 1 and 1…8 (default only 1 group is active).
•
Select local control for different setting groups from
SG Local Select
. Digital inputs, Logical inputs or outputs, stage starting-
tripping- or blocking, RTDs and object status information can be used.
•
Event masking for setting groups (masks are off as default). Only masked events appear to event list. Events cannot be cleared.
Setting group 1 has the highest and group 8 the lowest priority. Setting groups can be controlled with steady signal or pulses.
Figure 3.22
Group changing with pulse control only or with pulses and static signal.