7.5.2 Blackout recovery configuration
When a blackout is detected, all the GENSET controllers in SEMI mode are changed to AUTO mode.
Input
Assign the input under
Configure > Input/output
.
Table 7.10
Optional input
Function
I/O
Type
Details
Power management > Block blackout
start
Digital input Continuous
Blackout recovery is prevented in any section where this
input is activated.
Parameters
For a SHAFT generator controller, configure this parameter under
Configure > Parameters > Local power management >
Blackout > Blackout close
.
Parameter
Range
Default
Notes
Enable SG
blackout close
Not enabled,
Enabled
Not
enabled
Not enabled
: The power management system does not attempt to close the shaft
generator breaker if a blackout is detected.
Enabled
: When a blackout is detected, the shaft generator breaker can close
automatically if the shaft generator voltage and frequency are okay.
The blackout recovery sequence first tries to restore power by closing the bus tie
breaker, then connecting gensets, before trying to close the shaft generator breaker.
The sequence tries to connect the shaft generator before trying to connect to the
shore connection.
For a SHORE connection controller, configure this parameter under
Configure > Parameters > Local power management >
Blackout > Blackout close
.
Parameter
Range
Default
Notes
Enable SC
blackout close
Not enabled,
Enabled
Not
enabled
Not enabled
: The power management system does not attempt to close the shore
connection breaker if a blackout is detected.
Enabled
: When a blackout is detected, the shore connection breaker can close
automatically if the shore connection voltage and frequency are okay.
The blackout recovery sequence first tries to restore power by closing the bus tie
breaker, then connecting gensets, then closing the shaft generator breaker, before
trying to close the shore connection breaker.
For a BUS TIE breaker controller, configure this parameter under
Configure > Parameters > Local power management >
Blackout close
.
Parameter
Range
Default
Notes
Enable BTB
blackout close
Not enabled,
Enabled
Not
enabled
Not enabled
: The power management system does not attempt to close the bus
tie breaker if a blackout is detected.
Enabled
: When a blackout is detected on either busbar, the bus tie breaker can
close automatically if the voltage and frequency are okay on one of the busbars.
DESIGNER'S HANDBOOK 4189340911K UK