7.6.7 SHORE connection base load
INFO
A SHORE connection controller can only be assigned a base load.
The power management system distributes the load to keep the shore connection at the base load set point. The GENSET
controllers share the rest of the load.
Parameters
These parameters are only visible in a SHORE connection controller.
Configure the following parameter under
Configure > Parameters > Local power management > Shore connection base load >
Enable
.
Parameter
Range
Default
Notes
Enable SC base
load
Not enabled,
Enabled
Not enabled
Not enabled
: The shore connection cannot run in long-term parallel with
the gensets.
Enabled
: Base load is active for the SHORE connection controller. The
GENSET-SHORE parallel timer protection is disabled.
Configure the following parameter under
Configure > Parameters > Local power management > Shore connection base load >
Power set point
.
Parameter Range
Default Notes
Set point
10 to 120
%
90 %
The set point for the base load, as a percentage of the shore connection's nominal power.
If the system load is lower than this set point, the power management system de-loads the
gensets to the
Minimum limit
so that the shore connection can run as close to this set point as
possible.