7.9.17 Different power management rules activated
This alarm communicates that different power management rules apply to the same section.
The alarm is activated when two or more sets of power management rules apply to the section. A warning is displayed, and all the
controllers in the section are forced to switchboard control.
The alarm is always enabled. The alarm parameters are not visible in PICUS.
7.9.18 Network protocol incompatible
The alarm communicates that the controller has a different network protocol from the rest of the controllers in the system.
The alarm can for example activate when a controller with a newer software version than the other controllers is added to the
network. This includes different DEIF products in the same system, for example, PPU 300 controllers and PPM 300 controllers.
Update all the controllers in the system to the latest software.
The alarm action is
Warning
. You cannot see or change the alarm parameters.
7.9.19 PMS disabled due to an error
This alarm communicates that there is an internal error in the PMS software. PMS is disabled, and all the controllers in the system
are also forced into switchboard control.
The alarm action is
Warning
.
The alarm parameters are not visible in PICUS.