Table 8.11
Run coil parameters
Parameter
Range
Default
Comment
Run coil before
crank
0 s to 3 min
1 s
Optional. The controller activates the
Run coil
output for this time before the
Crank
output is activated.
During start
attempts
Follow crank,
Always on
Follow crank
Follow crank
: If the start attempt fails, the controller deactivates the
Crank
output and the
Run coil
.
Always on
: If the start attempt fails, the controller deactivates the
Crank
output. However, the
Run coil
remains activated until the maximum number
of start attempts is reached.
Optional. You must configure the
Engine > Stop coil
digital output to see these parameters. Configure these parameters under
Configure > Parameters > Engine > Start sequence > Stop coil
.
Table 8.12
Stop coil parameters
Parameter
Range
Default
Comment
During crank off
Activated, Not
activated
Activated
Activated
: The stop coil is activated during the start sequence if there is no
running detection and the crank is off.
Not activated
: The stop coil is not activated during the start sequence if there is
no running detection and the crank is off.
8.3.2 Engine start flowchart
The following flowchart shows the sequence that the controller uses to start a genset. The engine start sequences are described in
detail in the sections that follow.
This flowchart does not apply to switchboard control. Under switchboard control, if the operator presses the push-button
Start
on the display unit, the controller ignores the command and shows an info message.
DESIGNER'S HANDBOOK 4189340911K UK
Page 291 of 521