Table 8.36
Default parameters
Parameter
Range
Default
Enable
Not enabled, Enabled
Enabled
Latch
Not enabled, Enabled
Enabled
Action
Block
8.7.12 Start enable removed during start
The alarm response is based on the engine start-up sequence. This alarm is activated if the engine start-up procedure is interrupted
by the loss of the
Start enable
input before the engine has started.
Configure the parameters under
Configure > Parameters > Engine > Start sequence > Start enable remove during start
.
Table 8.37
Default parameters
Parameter
Range
Default
Alarm action
Warning
Enable
Not enabled, Enabled
Not enabled
8.7.13 Stop failure
This alarm is for genset stop failure.
The controller attempts to stop the genset by activating the
Stop coil
output (if present) or
alternatively, by deactivating the
Run coil
output (if present). If
Running detection
is still ON
after the delay time, the controller activates this alarm.
OFF
Running
detection
time
t
delay
ON
Configure the parameters under
Configure > Parameters > Engine > Stop sequence > Stop failure
.
Table 8.38
Default parameters
Parameter
Range
Default
Delay
0 s to 5 m
30 s
Enable
Not enabled, Enabled
Enabled
Action
Warning
8.7.14 Engine started (external)
This alarm is to alert the operator to an externally-initiated engine start.
The alarm is activated if the controller did not initiate an engine start, but
Running detection
shows that the engine is running.
On
Off
Running
detection
Time
Delay