8.7.17 Trip running hours notification
This alarm notifies the operator when the trip running hours exceeds the set point.
The alarm response is based on the
Trip running hours
counter.
0
Set
point
Value
time
Configure these parameters under
Configure > Parameters > Engine > Maintenance > Running hours trip
.
Table 8.42
Default parameters
Parameter
Range
Running hours trip
Set point
0 to 1,000,000 hours
500 hours
Enable
Not enabled, Enabled
Not enabled
Action
Warning
8.7.18 Voltage or frequency not OK
This alarm alerts the operator that the voltage or frequency is not in the required operation
range within a specified time after running detection is active.
A delay timer starts when running detection activates. If the voltage and frequency are not in
the required operation ranges when the delay timer expires the alarm activates.
The alarm response is based on the voltage and frequency from the source.
0
Value
time
t
delay
V OK
f OK
f
V
See
Configure > Parameters > [Source] > AC setup
. The parameters that the alarm is based on are under
Voltage and
frequency OK
. The alarm is configured under
Voltage or frequency not OK
.
The alarm action is always
Block
.
Table 8.43
Default parameters
Parameter
Range
Voltage or frequency not OK
Delay
1 s to 1 h
30 s
Enable
Not enabled, Enabled
Enabled
Inhibit(s)
•
Engine not running
•
[Breaker] closed
DESIGNER'S HANDBOOK 4189340911K UK
Page 318 of 521