This alarm sets the maximum time that a shore connection may be connected in
parallel to a shaft generator.
The power management system normally prevents a shore connection and a shaft
generator from connecting in the same section. This alarm is a safety feature, since
it is possible to for an operator to manually connect a shore connection and a shaft
generator. This can occur if the second equipment's breaker is closed manually, or
if the tie breaker between the two sections is closed manually.
This alarm is triggered when a shore connection and a shaft generator are
connected to the same busbar for longer than the delay time. The alarm delay timer
starts when the second equipment connects.
G
SHORE
connection
The alarm has a delay of 0.1 s. The alarm is always enabled. The alarm action is
Trip shore connection breaker
,
Latch enabled
. The
alarm parameters are not visible in PICUS.
11.5.8 SC-SC max. parallel time
This alarm is not active when
Multiple shore connections allowed
is
Enabled
.
DANGER!
Connecting two shore connections from different sources can release a large amount of energy. This can kill people and
destroy equipment.
This alarm sets the maximum time that a shore connection may run in parallel to
another shore connection.
If
Multiple shore connections allowed
is
Not enabled
, then the power management
system normally prevents two shore connections from connecting in the same
section. This alarm is a safety feature, since it is possible to for an operator to
manually connect two shore connections. This can occur if the second shore
connection's breaker is closed manually, or if the tie breaker between the two
sections is closed manually.
This alarm is activated when two shore connections are connected to the same
busbar for longer than the delay time. The alarm delay timer starts when the
second shore connection is connected.
SHORE
connection
SHORE
connection
The alarm has a delay of 0.1 s. If
Multiple shore connections allowed
is
Not enabled
, the alarm is always enabled. The alarm action
is
Trip shore connection breaker
,
Latch enabled
. The alarm parameters are not visible in PICUS.
INFO
To prevent a blackout, only the SHORE connection controller with the highest
Controller ID
trips its breaker.
DESIGNER'S HANDBOOK 4189340911K UK