Table 12.9
Active energy export counter parameters
Parameter
Range
Default Comment
Pulse every 1 kWh to 10 MWh 10 kWh The value when a digital output sends a pulse.
Pulse length 0.1 s to 1 h
1 s
The length of the pulse that is sent. This value should be long enough so the pulse
can be registered by the external counter.
Table 12.10
Reactive energy export counter parameters
Parameter
Range
Default
Comment
Pulse every 1 kvarh to 10 Mvarh 10 kvarh The value when a digital output sends a pulse.
Pulse length 0.1 s to 1 h
1 s
The length of the pulse that is sent. This value should be long enough so the pulse
can be registered by the external counter.
Table 12.11
Active energy import counter parameters
Parameter
Range
Default Comment
Pulse every 1 kWh to 10 MWh 10 kWh The value when a digital output sends a pulse.
Pulse length 0.1 s to 1 h
1 s
The length of the pulse that is sent. This value should be long enough so the pulse
can be registered by the external counter.
Table 12.12
Reactive energy import counter parameters
Parameter
Range
Default
Comment
Pulse every 1 kvarh to 10 Mvarh 10 kvarh The value when a digital output sends a pulse.
Pulse length 0.1 s to 1 h
1 s
The length of the pulse that is sent. This value should be long enough so the pulse
can be registered by the external counter.
Table 12.13
Active energy differential counter parameters
Parameter
Range
Default Comment
Pulse every 1 kWh to 10 MWh 10 kWh The value when a digital output sends a pulse.
Pulse length 0.1 s to 1 h
1 s
The length of the pulse that is sent. This value should be long enough so the pulse
can be registered by the external counter.
Table 12.14
Reactive energy differential counter parameters
Parameter
Range
Default
Comment
Pulse every 1 kvarh to 10 Mvarh 10 kvarh The value when a digital output sends a pulse.
Pulse length 0.1 s to 1 h
1 s
The length of the pulse that is sent. This value should be long enough so the pulse
can be registered by the external counter.
Table 12.15
Energy counter function and corresponding parameter full names
[Counter pulse]
[Counter]
Active energy export pulse 1
Active energy export
Reactive energy export pulse 1
Reactive energy export
Active energy import pulse 1
Active energy import
DESIGNER'S HANDBOOK 4189340911K UK