Specification
ON: -36 to -8 V DC, and 8 to 36 V DC
OFF: -2 to 2 V DC
Minimum pulse length: 50 ms
Impedance: 4.7 kΩ
Voltage withstand: ±36 V DC
Terminal connections
Relay outputs
: Terminals: Standard 45° plug, 2.5 mm
2
Wiring: 0.5 to 2.5 mm
2
(22 to 12 AWG), multi-stranded
Digital inputs
: Terminals: Standard 45° plug, 1.5 mm
2
Wiring: 0.5 to 1.5 mm
2
(28 to 16 AWG), multi-stranded
Torques and terminals
Module faceplate screws: 0.5 N·m (4.4 lb-in)
Connection of wiring to relay output terminals: 0.5 N·m (4.4 lb-in)
Connection of wiring to digital input terminals: 0.25 N·m (2.2 lb-in)
UL/cUL Listed: Wiring must be minimum 90 ºC (194 °F) copper conductors only.
Galvanic isolation
Between relay groups and other I/Os: 2210 V, 50 Hz for 60 s
Between digital input groups and other I/Os: 600 V, 50 Hz for 60 s
Ingress protection
Unmounted: No protection rating
Mounted in rack: IP20 according to IEC/EN 60529
Size
L 28 mm × H 162 mm × D 150 mm (1.1 in × 6.4 in × 5.9 in)
Weight
196 g (0.4 lb)
13.7.2 IOM3.1 terminal overview
Terminal
Symbol
Name
Type
1
Normally open
Relay output (250 V AC or 30 V DC, and 6 A)
2
Common
3
Normally closed
4
Normally open
5
Common
6
Normally closed
7
Normally open
8
Common
9
Normally closed
10
Normally open
11
Common
12
Normally closed
DESIGNER'S HANDBOOK 4189340911K UK
Page 438 of 521