13.9.4 Power supply characteristics
If the EIM power supply fails or is not connected, the PSM will supply power to the EIM. If the PSM power supply fails, the EIM will
run on its independent power supply. However, the EIM will not supply power to the PSM.
INFO
Class societies require an independent power supply for the EIM. The EIM must therefore not be connected to the same
power supply source as the PSM.
More information
See
Hardware characteristics and configuration
,
General characteristics
,
Power supply characteristics
for more
information.
13.9.5 EIM3.1 1 supply voltage low or missing alarm
This default alarm is for auxiliary power supply voltage protection.
The alarm is based on the power supply voltage measured by the EIM. The alarm is activated
when the power supply voltage is less than the set point for the delay time.
Set
point
Value
time
Delay
Configure the parameters under
Configure > Parameters > Hardware > EIM3.1 1 > Low voltage alarm
.
Table 13.31
Default parameters
Parameter
Range
EIM3.1 1 supply voltage low or missing
Set point
8.0 to 32.0 V DC
18.0 V DC
Delay
0 s to 1 h
1.0 s
Enable
Not enabled, Enabled
Enabled
Alarm action
Warning
13.9.6 EIM3.1 1 supply voltage high alarm
This default alarm is for auxiliary power supply voltage protection.
The alarm is based on the power supply voltage measured by the EIM. The alarm is activated
when the power supply voltage exceeds the set point for the delay time.
Set
point
Value
time
Delay
Configure the parameters under
Configure > Parameters > Hardware > EIM3.1 1 > High voltage alarm
.
Table 13.32
Default parameters
Parameter
Range
EIM3.1 1 supply voltage high
Set point
12.0 to 36.0 V DC
30.0 V DC
Delay
0 s to 1 h
1.0 s
DESIGNER'S HANDBOOK 4189340911K UK