Parameter
Range
Earth inverse time
over-current
Time multiplier setting (TMS)
0.01 to 100.0
1.0
Threshold
1.0 to 1.3
1.1
k (only used if custom curve is selected)
0.001 s to 2 min
0.14 s
c (only used if custom curve is selected)
0 s to 1 min
0 s
alpha (α, or a) (only used if custom curve is
selected)
0.001 to 1
0.02
Enable
Not enabled, Enabled
Enabled
Latch
Not enabled, Enabled
Enabled
Alarm action
Trip breaker
More information
See
Source AC protections
,
Inverse time over-current (ANSI 51N)
in this chapter for the calculation method, the
standard curves, and information about the definite time characteristic.
3.6.3 Neutral inverse time over-current (ANSI 51N)
Protection
IEC symbol (IEC60617)
ANSI (IEEE C37.2)
IEC 61850
Operate time
Neutral inverse time over-current
51N
-
This is the inverse time over-current alarm for the neutral current
measurement.
The alarm response is based on the unfiltered (except for anti-aliasing)
neutral current, as measured by the 4th current measurement.
The alarm response time depends on an approximated integral of the
current measurement over time. The integral is only updated when the
measurement is above the activation threshold.
Note: The diagram on the right is a simplified representation of this alarm.
The diagram does not show the integral over time.
t(I)
[s]
I [A]
I
NOM
1.1 I
NOM
Wiring
You must wire the 4th current measurement on ACM3.1 (terminals 15,16) to measure the neutral current.
More information
See
Wiring examples for controller functions
,
AC measurement wiring
,
System AC configuration
in the
Installation
instructions
for an example of how to wire the neutral current measurement.
INFO
The
Earth inverse time over-current
and
Neutral inverse time over-current
alarms each require the 4th current
measurement. You therefore cannot have both of these protections at the same time.
DESIGNER'S HANDBOOK 4189340911K UK