Alarms
Non-essential load (NEL)
•
Up to 3 non-essential loads per controller
•
Can connect each controller to the same 3 non-essential load breakers
NEL # over-current (1 alarm for each non-essential load)
NEL # under-frequency (1 alarm for each non-essential load)
NEL # overload 1 and 2 (2 alarms for each non-essential load)
NEL # reactive overload (1 alarm for each non-essential load)
Advanced blackout
prevention
P load sharing failure (low frequency)
P load sharing failure (high frequency)
Q load sharing failure (low voltage)
Q load sharing failure (high voltage)
Other
Forced to SEMI mode
Trip AVR output not configured
*Note: Only in GAM3.2.
8.7.2 Alarm actions
The GENSET controller has the following alarm actions:
•
Warning
•
Block
•
PMS-controlled stop
•
Trip generator breaker
•
Trip generator breaker and stop engine
•
Trip generator breaker and shutdown engine
•
Trip AVR*
•
Trip generator b AVR*
•
Trip generator b AVR + stop engine*
•
Trip generator b AVR + shutdown engine*
*Note: These alarm actions are only available if the
Trip AVR
digital output is configured.
8.7.3 Inhibits
The controller includes the following inhibits:
Table 8.27
Controller inhibits
Inhibit
Disables the alarm when ...
Engine running
Digital running detection
is ON.
Engine not running
Digital running detection
is OFF.
Generator breaker closed
The
Breakers > Generator breaker > Feedback > GB closed
digital input is activated.
Generator breaker open
The
Breakers > Generator breaker > Feedback > GB open
digital input is activated.
Generator voltage present
The generator voltage is above 10 % of the nominal voltage.
No generator voltage
The generator voltage is below 10 % of the nominal voltage.
Generator frequency
present
The generator frequency is above 10 % of the nominal frequency.
DESIGNER'S HANDBOOK 4189340911K UK
Page 310 of 521