Configure the parameters under
Configure > Parameters > Engine > Start sequence > Engine started (external)
.
Table 8.39
Default parameters
Parameter
Range
Default
Enable
Not enabled, Enabled
Enabled
Action
Warning
8.7.15 Engine stopped (external)
This alarm alerts the operator to an externally-initiated engine stop.
The alarm is activated if the controller did not initiate an engine stop, but
Running detection
shows that the engine has stopped.
On
Off
Running
detection
Time
Delay
Configure the parameters under
Configure > Parameters > Engine > Stop sequence > Engine stopped (external)
.
Table 8.40
Default parameters
Parameter
Range
Default
Enable
Not enabled, Enabled
Enabled
Latch
Not enabled, Enabled
Enabled
Action
Block
8.7.16 Total running hours notification
This alarm notifies the operator when the total running hours exceeds the set point.
The alarm response is based on the
Total running hours
counter.
0
Set
point
Value
time
Configure these parameters under
Configure > Parameters > Engine > Maintenance > Running hours total
.
Table 8.41
Default parameters
Parameter
Range
Running hours total
Set point
0 to 1,000,000 hours
500 hours
Enable
Not enabled, Enabled
Not enabled
Action
Warning