Table 13.43
Relationship between duty cycles and the PWM output
Duty cycle
Graph
100 %
Cycle
0
Voltage
[V]
time [s]
6.85
0.5
0.002
0.004
5.5
50 %
0
Voltage
[V]
time [s]
0.5
0.002
0.004
5.5
Cycle
6.85
12.5 %
0
5.5
Voltage
[V]
time [s]
0.5
0.002
0.004
0.006
Cycle
6.85
13.11.9 Digital input characteristics
More information
See
Hardware characteristics and configuration
,
General characteristics
,
Digital input characteristics and
configuration
.
13.11.10 Relay output characteristics
The first relay output (terminals 14,15) on GAM3.2 is reserved for the
Status OK
function. You cannot change the function for this
relay.
The four other relay outputs on GAM3.2 are configurable (that is, terminals 16,17; 18,19; 20,21; and 22,23 can be assigned any
function).
More information
See
Hardware characteristics and configuration
,
General characteristics
,
Relay output characteristics and
configuration
for more information.
13.11.11 GAM3.2 1 status not OK
This alarm communicates that the GAM3.2 cannot perform stand-alone regulation. This may be due to incomplete or incorrect
configuration.
DESIGNER'S HANDBOOK 4189340911K UK
Page 462 of 521