DEIF network: RJ45. Use an Ethernet cable that meets or exceeds the SF/UTP CAT5e
specifications. 100BASE-TX.
Torques and terminals
Module faceplate screws: 0.5 N·m (4.4 lb-in)
Connection of wiring to terminals: 0.5 N·m (4.4 lb-in)
UL/cUL Listed: Wiring must be minimum 90 °C (194 °F) copper conductors only.
Ingress protection
Unmounted: No protection rating
Mounted in rack: IP20 according to IEC/EN 60529
Size
L 36.8 mm × H 162 mm × D 150 mm (1.4 in × 6.4 in × 5.9 in)
Weight
214 g (0.5 lb)
13.12.2 PCM3.1 terminal overview
Terminal
Symbol
Type
Name
1
H
CAN high
CAN bus A (for future use)
2
CAN-A
CAN signal ground
3
L
CAN low
4
H
CAN high
CAN bus B (for future use)
5
CAN-B
CAN signal ground
6
L
CAN low
Table 13.46
PCM3.1 Example of Ethernet connections
Connection
Symbol
Type
Name
1
RJ45
DEIF network to another controller
2
RJ45
DEIF network to another controller
3
RJ45
Service PC
4
RJ45
Display unit
5
RJ45
•
DEIF network
•
SCADA
•
AMS
•
Modbus TCP/IP
INFO
The Ethernet ports are fully interchangeable.
13.12.3 Controller temperature too high
This is a built-in alarm for the controller internal temperature, as measured on PCM3.1. The alarm is triggered when the controller
internal temperature is higher than 80 °C (176 °F). The alarm action is
Warning
. The alarm parameters are not visible.
INFO
If the controller operates at internal temperatures higher than 80 °C (176 °F), the performance and the lifetime of the
controller is significantly reduced.