1. Upon receipt of the battery, if there are signs of rough handling

or of electrolyte leakage, file a claim with the carrier and advise
your Deka representative.

The electrolyte level should normally be above the perforated
separator protector, which can be seen in the cell when the vent
caps are removed. However vibrations during shipping often
shake enough gas out of the cell that the electrolyte level may
drop below the separator protector, especially on taller cells. If
the electrolyte level is still above the top of the plates and can
be seen with a flashlight through the holes in the separator
protector, the battery may be given its initial charge without
adjusting the electrolyte level.

If the electrolyte level is not visible or is below the top of the
plates, check again for leaking cells and call your Deka
representative before charging the battery.

2. The battery shall be charged on a properly rated fast charger

that is mutually agreed upon by the user and Deka.

3. The “Battery Type Identification” shown on the battery (E, EO,

EE, EX) should match the “Battery Type Identification” specified
on the truck nameplate.

4. Make sure that the battery “SERVICE WEIGHT,” which is

stamped below the lifting hole in the steel tray, falls within the
battery weight range shown on the truck nameplate. East Penn
Manufacturing Co. cannot be responsible for determining that
the battery weight is sufficient to counter-balance your
particular truck.

5. Prior to placing the battery in service, it should be given an

equalizing charge. Near the end of the charge, check to make
sure that the electrolyte levels of all cells are visible and above
the separator protector. The full charge specific gravity is 
1.280 to 1.295 when temperature corrected to 77°F (25°C).

6. Upon installation in the truck, battery restraints should be

adjusted to restrict movement of the battery to no more than
1/2" in a horizontal direction. An insulated spreader bar should
be used any time the battery is lifted or hoisted.

7. Batteries normally should not be discharged more than 80% of

their rated capacity for longest service life. Section III of DEKA
INDUSTRIAL BATTERY SERVICE MANUAL (0656) gives
detailed information for your specific battery type.

8. The battery may be opportunity fast charged as required on a

daily basis. The battery must receive minimum 80% preferably
100% recharge every twenty-four (24) hour period. The battery
shall receive an equalize charge (greater than 100%) on a
weekly basis. All vent caps should be kept in place and the steel
battery trap cover or the truck compartment cover kept open
while charging.

9. A copy of the DEKA INDUSTRIAL BATTERY SERVICE MANUAL

(0656), which gives more detailed information on the Operation
and Maintenance of motive power batteries, can be obtained
from your Deka representative or by visiting

www.dekabatteries.com.

Congratulations on your choice of a new Deka industrial battery.

The complete line of Deka industrial batteries incorporates

every feature required by today’s user of electric industrial trucks. Designed with East Penn engineering technology and 

built by master

battery craftsmen 

according to strict quality assurance guidelines, Deka industrial batteries are the 

finest available

to meet today’s

material handling requirements. Deka precision construction provides new equipment performance throughout a long life. This battery
has been inspected prior to shipment to insure that it meets your specifications as ordered. By following the operating and maintenance
instructions, you will be insuring optimum life and performance of your new Deka industrial battery.

OPERATING INSTRUCTIONS