5
MPI-300
Installation & Operations Manual
SECTION 5 REPLACEMENT PARTS
AND ORDER INFORMATION
5A. Ordering information:
For replacement parts call DEL at
1-800-676-1335
or for international call
805-541-1601.
Be prepared with the following information:
· Customer Name
· Customer Address
· DEL Model Number
· DEL Serial Number
· Date Purchased
· Proof of Purchase
5B. Standard replacement parts list:
1. Compressor rebuild kit .......................2-0875-01
2. Cabinet Intake Air Filter Element ............. 7-1153
3. Cabinet Exhaust Air Filter Element ......... 7-1152
4. Compressor Air Filter Cartridge ............... 7-1132
5. Ozone Generation Cell ............................ 9-0925
SECTION 6 OZONE OVERVIEW
AND SAFETY PROCEDURES
6A. Ozone Use and Technology Overview
6A-1. Relative Strength of Ozone
The following compares the strengths of several
common oxidizing reagents:
Oxidizing Reagent EOP vs. Cl
2
Elemental Fluorine ............................2.25
Hydroxyl Radical ...............................2.05
Ozone ...............................................1.52
Hydrogen Peroxide ...........................1.30
Hypochlorite .....................................1.10
Chlorine ............................................1.00
Chlorine Dioxide ...............................0.93
Bromine ............................................0.57
The following compares the CT values for water of
ozone versus forms of chlorine:
Microorganism
Disinfectant
Ozone
(pH 6-7)
Preformed
Chlormine
(pH 8-9)
Chlorine
Dioxide
(pH 6-7)
Free
Chlorine
(pH 6-7)
E. Coli
0.02
95-180
0.4-0.75
0.034-0.05
Polio 1
0.1-0.2
770-3740
0.2-6.7
1.1-2.5
Rotavirus
0.006-0.06
3810-6480
0.2-2.1
0.01-0.05
G. lamblia cysts
0.5-0.6
--
--
47->150
G. muris cysts
1.8-2.0
1400
7.2-18.5
30-630
6A-2. Materials Selection
Materials
Aqueous Ozone
0-3 ppm Freshwater
Metals:
Copper
Brass
316L Stainless Steel
5
5
5555
Plastics:
ECTFE (Halar)
PTFE (Teflon)
PVC (rigid)
PVC (flexible)
PVDF (Kynar)
5555
5555
555
555
5555
Elastomers:
FPM (Viton)
555
(gasket)
LEGEND:
5
= Not Recommended
55
= Fair
555
= Good
5555
= Very Good
6A-3. Micro-Flocculation and Oxidation
Ozone oxidizes the following metals (know as
micro-flocculation), enabling their removal via
filtration:
• Iron
• Copper
• Manganese
• Zinc
• Arsenic
Ozone neutralizes “nuisance” compounds - most
commonly, hydrogen sulfide.
6A-4. Factors Affecting Sanitation
The following factors will affect the ability of ozone
to effectively act as a sanitizer:
• Type and level of contaminant
• Physical/chemical parameters of the environs
• Exposure time
• Temperature
• Concentration
• Water chemistry and pH
• Cleanliness
• Microbial attachment
6B. General Safety Information
6B-1. Ozone Properties
• Colorless to blue gas (greater than -169°F)
• Characteristic odor often associated with electri-
cal sparks or lightning in concentrations of ..less
than 2 PPM
• Severe irritant above 1-2 PPM
• Generally exists as a gas
• Highly chemically reactive
• Non-flammable, non-carcinogenic
• Hazardous polymerization can occur
• Spontaneously decomposes to oxygen gas
Summary of Contents for MPI-300
Page 13: ...10 MPI 300 Installation Operations Manual APPENDIX A DAILY DATA LOG...
Page 14: ...11 MPI 300 Installation Operations Manual APPENDIX A...
Page 15: ...12 MPI 300 Installation Operations Manual APPENDIX B EMERGENCY INFORMATION...
Page 16: ...13 MPI 300 Installation Operations Manual...
Page 17: ...14 MPI 300 Installation Operations Manual APPENDIX C SAFETY...