The screen displays that the system is collecting data. When the data collection is
completed, the screen displays status information for the fans.
acme-dp4400-ACM:~ # showfru fan
Collecting Data............
_______________________________________
| ID| Status| Redundancy| PWM| Reading |
|======================================|
| 1 | OK | Full | 36%| 9000 RPM|
| 2 | OK | Full | 36%| 9000 RPM|
| 3 | OK | Full | 36%| 9000 RPM| *
| 4 | OK | Full | 38%| 8880 RPM|
| 5 | OK | Full | 38%| 9000 RPM|
| 6 | OK | Full | 38%| 9000 RPM|
2. Verify the status for all fans is "OK".
Install the system cover
Procedure
1. Align the tabs on the system cover with the guide slots on the system.
2. Push the system cover latch down.
The system cover slides forward, the tabs on the system cover engage with the guide slots
on the system and the system cover latch locks into place.
3. Using a flat or Phillips head screwdriver, rotate the latch release lock clockwise to the
locked position.
Figure 22 Install the system cover
Slide the system into the cabinet
Procedure
1. At the front of the cabinet, push the system inward until the lock levers click into place.
Remove and replace assemblies
Dell EMC Integrated Data Protection Appliance DP4400 Service Procedures
37