Figure 10 Installing the cooling fan
After you finish
1.
Install the X400 capacity cube cover
.
2.
Slide the X400 capacity cube into the rack
3. In the PowerProtect Data Manager UI, on the Appliance page, verify that the capacity cube
node status is online.
l
If the capacity cube node status is not online, go to the Alerts and Events page, select the
checkbox next to the alert related to the cooling fan replacement procedure, and click
Acknowledge.
l
On the Appliance page, verify that the capacity cube node status is online.
Front bezel replacement
Removing the front bezel
The procedure to remove the front bezel with the LCD panel and the front bezel without the LCD
panel is the same.
Before you begin
1. Follow the
.
Procedure
1. Unlock the bezel by using the bezel key.
2. Press the release button, and pull the left end of the bezel.
3. Unhook the right end, and remove the bezel.
X400 capacity cube CRU procedures
22
PowerProtect X400 Appliance Customer Replaceable Unit (CRU) Procedures