NOTE:
The rack installation ears are not suitable for grounding.
To connect the ground cable to the switch:
1. Cut your user-supplied ground cable to the wanted length.
The cable length must facilitate proper operation of the fault interrupt circuits. Use the shortest cable route allowable.
2. Crimp the ground cable inside the ground lug.
3. Attach the other end of the ground cable to a suitable ground point such as the rack or cabinet.
The rack installation ears are not a suitable grounding point.
Desktop
One mounting option is to place the full-width N3200-ON Series switch on a desktop.
The mounting supplies for this installation ship with the switch. To use the full-width N3200-ON Series switch on a desktop, first attach
the four small rubber feet to the underside of the switch.
1. Locate the four rubber feet shipped with the switch.
2. Remove the paper backing on the bottom of one of the rubber feet.
3. Adhere the rubber foot to one of the four round position marks on the underside of the switch.
4. Repeat the process for the remaining three rubber feet.
5. Turn the switch over and place on a desktop.
Two-post five-inch-offset full-width switch
installation
You must order the mounting supplies for this installation separately.
1. Locate the mounting brackets and screws that ship with the switch.
18
N3200-ON Series switch installation