63
Specifications
|
Specifications
This chapter provides the following specifications:
S
Model list
S
Dimensions and weights
S
Electrical input and output
S
Environmental and safety
S
Battery
S
UPS block diagram
Table 10. UPS Model List
120V Models
208V Model
230V Models
UPS Models
2700R Telco LV (K803N),
2700W
2700R Telco HV-US
(H950N), 2700W
2700R Telco HV (J728N),
2700W
External Battery Module
(EBM)
2700R EBM (H967N), 96 Vdc
Table 11. Dimensions and Weights
UPS
EBM Model
UPS Dimensions
(W
H
D)
438.0
171.5
433.0 mm
17.2
”
6.8
”
17.0
”
(4U)
438.0
171.5
433.0 cm
17.2
”
6.8
”
17.0
”
(4U)
Weights
36.9 kg (81.4 lb)
51.8 kg (114.2 lb)
Table 12. Electrical Input
120V Models
208V Models
230V Models
Nominal Voltage
120V
208V
230V
Voltage Range
82–144V auto-sensing
155–255V auto-sensing
160–286V auto-sensing
Nominal Frequency
50/60 Hz auto-sensing,
±
3 Hz
Efficiency (Normal Mode)
>95%
Noise Filtering
Full-time EMI/RFI filtering
Connections
2m, L5-30P attached
power cord
IEC 320-C20 input
connector, 16A
IEC 320-C20 input
connector, 16A
7