Power Requirements
There are two types of power supplies: Power Supply 1200W-AC and Power Supply 1600W-AC. The
minimum and the redundant power supplies required to operate is listed in the table below. Dell
Networking recommends the redundancy configuration.
The C7004/C150 needs at least one power supply to operate. However, Dell Networking recommends a
one-plus-one redundancy configuration. That is, use a minimum of two AC or DC power supplies; one is
for redundancy.
The C7004/C150 power requirements are given below:
Shipping and Storing Components
If you do not install your C7004/C150 system and components immediately, Dell Networking
recommends you properly store components (including all extra field-replaceable parts) until you are
ready to install them.
Follow these indoor storage guidelines:
•
Storage temperature should remain constant ranging from -40°F to 158°F (-40°C to 70°C).
•
Non-condensing relative humidity should be maintained with 5 to 95%.
•
Store on a dry floor, away from direct sunlight, heat, and air conditioning ducts.
•
Store in a dust-free environment.
Voltage
Minimum PSUs
Minimum with
Redundant PSUs
Power Supply 1200W-AC/Power Supply
1600W-AC
100-120
1 2
Power Supply 1200W-AC
200-240
1
2
Power Supply 1600W-AC
200-240
1
2
Table 3-1. System Specifications
Parameter
Specifications
Nominal Input Voltage
100-240 V 50/60 Hz
Maximum AC Power Supply Input Current
(Based on 1200 W output for 100/120 V and
1600 W 200/240 V lines)
14 A @ 100 V per AC Power Supply
11 A @ 120 V per AC Power Supply
9 A @ 200 V per AC Power Supply
7 A @ 240 V per AC Power Supply
Maximum System Power Input
6,897 KVA @ 100/120 V
7,315 KVA @ 200/240 V
Maximum Thermal Output at 100/120V
5,618 BTU/hour
Maximum Thermal Output at 200/240V
5,304 BTU/hour
Summary of Contents for C7004/C150
Page 1: ...Installing and Maintaining the C7004 C150 System ...
Page 6: ...6 Contents w w w d e l l c o m s u p p o r t d e l l c o m ...
Page 14: ...14 Preparing the Site w w w d e l l c o m s u p p o r t d e l l c o m ...
Page 18: ...18 Installing the C7004 C150 Chassis w w w d e l l c o m s u p p o r t d e l l c o m ...
Page 28: ...28 Management Cable Pinout w w w d e l l c o m s u p p o r t d e l l c o m ...
Page 40: ...40 Installing DC Power Entry Modules w w w d e l l c o m s u p p o r t d e l l c o m ...
Page 44: ...44 Powering Up w w w d e l l c o m s u p p o r t d e l l c o m ...
Page 61: ...System Specifications 61 Figure B 2 Chassis Dimensions Depth 15 5 inches ...
Page 70: ...70 Contacting Technical Support w w w d e l l c o m s u p p o r t d e l l c o m ...
Page 71: ......
Page 72: ...w w w d ell com support dell com Printed in the U S A ...