Installing B Series directors
63
Installing Directors into the EC-1700 Cabinet
ED-DCX8510-4 and
ED-DCX-4S-B
Plug the "right angle" (L) connectors into the system as shown: Cable
from
LEFT SIDE
into top (PS1). Cable from
RIGHT SIDE
to bottom
(PS2).
Figure 42
Connectors’ positioning for ED-DCX8510-4 and ED-DCX-4S-B
Installing the Ethernet Hub
The ethernet hub installs with two mounting ears on the hub chassis
and attaches to the cabinet via 2 screws (
) and clip nuts on
the left and right side vertical mounting rails in the top U of the
cabinet.
Note:
The ethernet hub (model # SP-HUB-ETH) in the EC-1700-B is an
optional item. If no ethernet hub was ordered then connect the ethernet
cables directly to the customer's network ports. If the hub is installed in the
cabinet, then connect them as described below. Note prenumbered ethernet
cables are not included the cabinet. The customer will need to provide
standard CAT-5 ethernet cables.
Connect the hub cables to the director as follows:
◆
For one director:
• Dress the connected ethernet cables through the circular
opening in the cable management tray (