Fan specifications
The PowerEdge MX7000 enclosure supports four front accessible hot-swap cooling fans and five rear accessible hot-swap cooling
fans. The cooling fan assembly ensures that the key components of the server such as the sleds, Fabrics, and I/O modules get
adequate air circulation to keep them cool. A cooling fan failure can result in overheating and may lead to damage.
Table 16. Supported fans
Fan location
Front
Rear
Size
60 mm
80 mm
Number of fans
4
5
Redundancy
3+1
4+1
PSU specifications
The PowerEdge MX7000 enclosure supports up to six AC power supply units (PSUs).
Table 17. PSU specifications
Description
Specification
PSU
6 x 3000 W AC
Class
Platinum
Heat dissipation (maximum)
1205 BTU/hr
Frequency
50/60 Hz
Voltage
100–240 V AC, autoranging
Current
6 x 16 A
Inrush current
120 A per power supply for 10 ms or less.
Connector
C22 AC power connector
CAUTION: Mixed high line and low line AC inputs in the same enclosure is not supported. If this occurs, the enclosure
disables the PSUs with the lowest input. If there is an equal number of high lines, and low line PSUs the high line PSUs
are enabled.
NOTE: Heat dissipation is calculated using the PSU wattage rating.
NOTE: In an ideal input voltage condition and over the entire enclosures ambient operating range, the inrush current may
reach 120 A per power supply for 10 ms or less.
NOTE: This enclosure is also designed to connect to the IT power enclosures with a phase-to-phase voltage not
exceeding 240 V.
Ports and connectors specifications
USB ports
The PowerEdge MX7000 enclosure supports two Type A, USB 2.0 ports on the front panel.
Mini DisplayPort
The PowerEdge MX7000 enclosure supports one Mini DisplayPort (mini DP) on the front panel.
36