Site preparations
The S5148F-ON switch is suitable for installation as part of a common bond network (CBN).
You can install the switch in:
●
Network telecommunication facilities
●
Data centers
●
Other locations where the National Electric Code (NEC) applies
For more information about switch specifications, see
.
NOTE:
Install the S5148F-ON switch in a rack or cabinet before installing the components.
Topics:
•
•
•
•
•
•
Site selection
Install the switch equipment in restricted access areas.
A restricted access area is one in which service personnel can only gain access using a special tool, lock, key or other means of
security. The authority responsible for the location controls access to the restricted area.
Ensure that the area where you install your switch meets the following safety requirements:
●
Near an adequate power source. Connect the switch to the appropriate branch circuit protection according to your local
electrical codes.
●
Switch environmental temperature range is from 0°C to 45°C (32°F to 113°F).
●
Relative humidity is from 5 to 85 percent non-condensing.
●
In a dry, clean, well-ventilated, and temperature-controlled room, away from heat sources such as hot air vents or direct
sunlight.
●
Away from sources of severe electromagnetic noise.
●
Inside the restricted access area, positioned in a rack or cabinet, or on a desktop with adequate space in the front, back, and
sides for proper ventilation and access.
●
Install the switch in Information Technology Rooms in accordance with Article 645 of the National Electrical Code and NFPA
75.
For more information about switch storage and environmental temperatures, see
Cabinet placement
Install the S5148F-ON switch only in indoor cabinets designed for use in a controlled environment.
Do not install the switch in outside cabinets. For cabinet placement requirements, see
.
The cabinet must meet minimum size requirements. Airflow must be in accordance with the Electronic Industries Alliance (EIA)
standard. Ensure that there is a minimum of 5 inches (12.7 cm) between the intake and exhaust vents and the cabinet wall.
3
Site preparations
13