Ra c k I n s t a l l a t i o n G u i d e
1-19
2
Installing the slide assemblies in the rack
•
Center-mount installation
•
Flush-mount installation
3
Installing the system in the rack
4
Installing the cable-management arm
5
Routing cables
Marking the Rack
You must allow 1 U (44 mm, or 1.75 inch) of vertical space for each system you install in the
two-post rack.
Universal-Hole Spacing Racks
Racks with universal-hole spacing have an alternating pattern of three holes per rack unit
with center-to-center hole spacing (beginning at the top hole of a 1-U space) of 15.9 mm,
15.9 mm, and 12.7 mm (0.625 inch, 0.625 inch, and 0.5 inch) for the front and back vertical
column of holes (see Figure 1-13).
F i g u r e 1 - 1 3 .
Tw o - P o s t , O p e n - F r a m e R e l a y R a c k U n i v e r s a l - H o l e S p a c i n g
Wide-Hole Spacing Racks
Racks with wide-hole spacing have an alternating pattern of two holes per rack unit with
center-to-center hole spacing (beginning at the top hole of a 1-U space) of 31.7 mm and
12.7 mm (1.25 inches and 0.5 inch) for the front and back vertical columns of holes (see
Figure 1-14).
12.7 mm (0.5 inch)
15.9 mm (0.625 inch)
15.9 mm (0.625 inch)
1 U (44 mm or 1.75 inches)
JO525bk0.book Page 19 Monday, January 27, 2003 12:29 PM
Summary of Contents for PowerVault 725N
Page 6: ...6 Contents JO525bk0 book Page 6 Monday January 27 2003 12 29 PM ...
Page 42: ...6 Sommaire JO525fbk0 book Page 6 Monday January 27 2003 12 55 PM ...
Page 82: ...6 Inhalt JO525bk0 book Page 6 Monday January 27 2003 1 11 PM ...
Page 122: ...6 目次 JO525jbk0 book Page 6 Monday January 27 2003 3 13 PM ...
Page 160: ...6 Contenido JO525sbk0 book Page 6 Monday January 27 2003 4 29 PM ...