13
4. INSTALLATION
DELIVERY
Check condition of equipment on delivery. Contact the supplier and carrier immediately if the
packaging or unit is damaged.
INITIAL INSPECTION
Unpack the UPS carefully, notice the packing method, and retain the box and packing material. (If you
must return the UPS at any time, repack it how it was originally shipped.) Visually inspect the UPS for
damage which may have occurred during shipment. If there is damage or anything is missing, contact
the dealer from whom you purchased the unit, and save the packaging for future shipment. When the
unit has passed the initial inspection, record the purchase date on the back panel of the unit and in the
space provided in the front of the manual.
Appendage: 1. User manual
×
1
2. RS232 CABLE
×
1
3. UPSentry CD
×
1
4. Battery cable
×
1
STORAGE AND BATTERY MAINTENANCE
If the ON-LINE UPS is to be stored prior to installation, it should be placed in a dry, ventilated area
where it will not be exposed to dirt, moisture or other contaminates.
Extreme storage temperatures:
-20
°
C to + 60
°
C without battery.
-20
°
C to + 45
°
C with battery for a short period.
Maximum storage period for battery: 6 months at 20
°
C or 3 months at 30
°
C.
Important: 1. When the ON-LINE UPS is to be stored for longer than 3 months, it is recommended to
recharge the battery every 3 months.
2. Do not stack these units.
VENTILATION
The ON-LINE UPS is intended for installation in a temperature and humidity controlled indoor area free of
conductive contaminants. Ambient temperature must not exceed 40°C (104°F).
IMPORTANT: maximum battery life is obtained by placing the battery in a room at an ambient
temperature of 15
°
C to 25
°
C. Battery life decreases by half for every 10
°
C above 25
°
C.