SELECTION OF CABLES:
Cable cross-sections depend on carried current:
Current carried:
MODEL
RATED INPUT
CONNECTOR WIRES
RATED OUTPUT CONNECTOR WIRES
5/ 7 KVA
8AWG or 8mm
2
8AWG or 8mm
2
9/ 11 KVA
6AWG or 14mm
2
6AWG or 14mm
2
SELECTION OF CONDUIT AND BUSHING:
In accordance with National Electrical Code, please install all the wiring with suitable conduit and bushing.
The suggestion is:
Conduit: Flexible metal conduit sized one inch.
Bushing: Overall diameter is 40.5mm, height is 13.1mm.
UPS SETTING CABINETS FIX:
1. To fix the UPS with hang up ear. (Fig. 1)
2. To adjust fit length track location and enhance to fix in cabinet inner, then fix hang up ear in track. (Fig. 2)
If need to fix components for cabinets, please contact agent in the locality.
3. Connect two pieces of “support stand”. Prepare two sets of support stand combination.
Notice the suitable width for UPS racks!
4. Put UPS among the support stand combination. (Fig. 3)
Be sure to keep at least 30cm distance on the front and rear side.
←
Fig. 3
Fig.2
↑
Fig. 1