INPUT AND OUTPUT CONNECTION:
When connecting the cable, please notice that:
1. Before connecting, turn off the UPS and cut off not merely the AC source but also the battery.
2. Ensure the cable is fitted. The minimum tightening torque shall not be less than 35 lbs with a cable sleeve & secured by the
connector clamp.
3. Connect the EARTH wire to the terminal marked with “ G ” .
The connective methods of input and output:
(A) Europe model
5KVA/ 7 KVA/ 9 KVA/ 11 KVA
L
OUTPUT
INPUT
T
Rectifire Input
200Vac
208Vac
220Vac
230Vac
240Vac
Bypass input
N
S
R
N
Connect to
EARTH
R
11KVA (3:1)
G
L
O U T P U T
IN P U T
L 1
R e c tifire In p u t
200Vac
208Vac
220Vac
230Vac
240Vac
Bypass input
N 1
L 2
G
N
Connect to
EARTH