P/N:5011316802

Summary of Contents for 11KVA

Page 1: ......

Page 2: ... 4 INSTALLATION 13 Delivery 13 Initial inspection 13 Storage and battery maintenance 13 Ventilation 13 5 OPERATION 17 Inverter ON OFF 17 LCD function select switch 19 Parameter set up mode 21 Operation on bypass voltage 22 Operation under shutdown 22 Verifying the battery condition 23 Operation of manual bypass switch 23 6 COMMUNICATION INTERFACE 24 RS 232 24 Dry contact 24 Remote emergency power ...

Page 3: ...y UPS before working on the circuit A readily accessible disconnect device shall be incorporated in the fixed wiring HIGH LEAKAGE CURRENT Earth connection essential before connecting supply Federal Communications Commission Interference Statement This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules These limits are des...

Page 4: ... CLASS A IEEE C6241 Category B IEC 1000 2 2 EN 61000 4 2 LEVEL3 EN 61000 4 3 LEVEL3 EN 61000 4 4 LEVEL4 EN 61000 4 5 LEVEL4 CNS 13438 CLASS A SYMBOL PROTECTIVE GROUNDING TERMINAL A TERMINAL WHICH MUST BE CONNECTED TO EARTH GROUND PRIOR TO MAKING ANY OTHER CONNECTION TO THE EQUIPMENT A TERMINAL TO WHICH OR FROM WHICH A DIRECT CURRENT OR VOLTAGE MAY BE APPLIED OR SUPPLIED THIS SYMBOL INDICATES THE W...

Page 5: ...and LCD message display providing operation and status information By means of manual and static bypass switches to switch to AC mains Static bypass supply incorporates surge suppression and EMI filter Remote emergency power off EPO When activated EPO UPS output will be powered off The UPS into a safe shutdown condition Automatic restart The UPS will start again on inverter automatically when ac l...

Page 6: ...elect to set different output frequency voltage operation mode and UP DOWN select LCD frame if press more than 3 seconds will detecting battery 4 BACKLIT LCD DOT MATRIX DISPLAY 16 2 character display Indicate the operating status I P O P voltage battery voltage 5 NORMAL LED Display UPS DC AC circuit is working or not 6 BATTERY LED Display UPS power source from battery 7 BYPASS LED Display bypass v...

Page 7: ...NDUCTORS ONLY REFER TO USER S MANUAL FOR DO NOT DISCONNECT EXTERNAL UNDER LOAD CAUTION 240VDC BATTERY INPUT AC INPUT BREAKER BREAKER BYPASS CURRENT L L1 N N1 L2 SNMP EPO RS 232 DRY CONTACT CURRENT CHARGE BYPASS MANUAL 220 230 240V 50 60HZ AC OUTPUT 200 208 TORQUING SPECIFICATIONS USE COPPER CONDUCTORS ONLY REFER TO USER S MANUAL FOR 220 230 240V 50 60HZ AC INPUT 200 208 UNDER LOAD BATTERY INPUT DO...

Page 8: ...CT UNDERLOAD 240VDC CAUTIO N EXTERNAL REFER TOUSER SMANUALFOR COPPER CONDUCTORSONLY TORQ UINGSPECIFICATIONS USE 220 230 240V 50 60HZ 200 208 AC INPUT SPECIFICATIONS USE REFER TO USER S MANUAL COPPER CONDUCTORS ONLY DO NOT DISCONNECT EXTERNAL BATTERY INPUT DRY CONTACT EPO RS 232 SNMP T AC OUTPUT 240V 50 60HZ 200 208 220 230 N L N AC INPUT BREAKER CHARGE CURRENT 200 208 220 230 240V 50 60HZ AC INPUT...

Page 9: ...S FOR COOLING AIR VENTILATION OF UPS 6 TRUE RS 232 INTERFACE PORT FOR DETAILS PLEASE REFER TO SECTION 6 7 DRY CONTACT INTEERFACE PORT FOR DETAILS PLEASE REFER TO SECTION 6 8 REMOTE EMERGENCY POWER OFF FOR DETAILS PLEASE REFER TO SECTION 6 9 SNMP CARD FOR DETAILS PLEASE REFER TO SECTION 6 10 BYPASS INPUT BREAKER UPS POWER FROM BYPASS INPUT AND TO PROVIDE SAFE PROTECTION 11 AC INPUT BREAKER UPS POWE...

Page 10: ...NPUT PROTECTION CIRCUIT BREAKER 40A 1 pole x 2 for Europe 40A 1 pole x 2 for Europe 40A 2 pole x 1 for USA 63A 1 pole x 2 for Europe 63A 2 pole x 1 for USA 63A 1 Pole 1 25A 3 Pole 1 for Europe 4 OUTPUT 4 1 OUTPUT VOLTAGE RMS VOLTAGE 200 208 220 230 240V STATIC REGULATION 2 4 2 HARMONIC DISTORTION 3 4 3 OVERLOAD CAPABILITY 102 CONTINUOUS 102 125 1MINUTE 125 150 30 SECONDS 150 immediate 16 CYCLES 4 ...

Page 11: ...220VDC 3 5 8 BATTERY SHUTDOWN VOLTAGE 212VDC 3 discharge exceed 1hour 200VDC 3 5 9 BACK UP TIME 9MIN 4000W 12V 7Ah x 20PCS 7MIN 4900W 12V 7Ah x 20PCS 7MIN 6600W 12V 9Ah x 20PCS 5MIN 8000W 12V 9Ah x 20PCS 5MIN 7700W 12V 9Ah x 20PCS 6 OPERATION 6 1 TRANSFER TIME ON LINE MODE MAIN POWER FAILURE 0ms MAIN POWER RECOVER 0ms INVERTER TO BYPASS 1ms BYPASS TO INVERTER 1ms ECONOMY MODE MAIN POWER RECOVER 0m...

Page 12: ...nches 590 3mm 23 24 inches WIDTH W 444 5mm 17 5inches HIGHTH H 130 6mm 5 14inches NET WEIGHT 20 5KG 45 194 LB 24 5KG 54 013LB 27KG 59 524 LB BATTERY CABINET WEIGHT 69 5KG 153 2LB 12 EMVIRONMENT 12 1 AMBINET OPERATING TEMPERATURE 0o C 40 o C 32 o F 104 o F 12 2 AMBIENT STORAGE TEMPERATURE 20 o C 40 o C 36 o F 104 o F 12 3 RELATIVE HUMIDITY 5 95 H 13 STANDARDS 13 1 UL 1778 MEET 13 2 CSA 22 2 107 MEE...

Page 13: ...9 1015 503 335 291 216 155 138 110 103 93 BBR120920 10 1156 575 374 250 195 178 147 124 110 103 J 9K 6600 Watts 9000VA 660W 1320W 1980W 2640W 3300W 3960W 4620W 5280W 5940W 6600W BBR120920 1 107 51 30 22 17 14 12 10 8 7 BBR120920 2 205 109 76 53 45 30 26 22 19 17 BBR120920 3 361 183 111 88 67 54 46 36 30 26 BBR120920 4 513 255 170 113 97 78 62 54 48 41 BBR120920 5 673 319 212 144 116 101 87 68 58 5...

Page 14: ...0 BBR120720 9 1428 755 477 348 268 232 174 161 128 116 BBR120720 10 1650 831 550 381 301 255 215 184 164 127 J 5K 4000 Watts 5000VA 400W 800W 1200W 1600W 2000W 2400W 2800W 3200W 3600W 4000W BBR120720 1 170 91 49 33 25 21 16 13 11 9 BBR120720 2 358 170 110 84 60 46 39 31 27 25 BBR120720 3 540 260 170 120 100 75 64 57 52 45 BBR120720 4 740 355 240 170 122 110 95 84 68 60 BBR120720 5 892 505 290 235 ...

Page 15: ... CABLE 1 3 UPSentry CD 1 4 Battery cable 1 STORAGE AND BATTERY MAINTENANCE If the ON LINE UPS is to be stored prior to installation it should be placed in a dry ventilated area where it will not be exposed to dirt moisture or other contaminates Extreme storage temperatures 20 C to 60 C without battery 20 C to 45 C with battery for a short period Maximum storage period for battery 6 months at 20 C ...

Page 16: ...le metal conduit sized one inch Bushing Overall diameter is 40 5mm height is 13 1mm UPS SETTING CABINETS FIX 1 To fix the UPS with hang up ear Fig 1 2 To adjust fit length track location and enhance to fix in cabinet inner then fix hang up ear in track Fig 2 If need to fix components for cabinets please contact agent in the locality 3 Connect two pieces of support stand Prepare two sets of support...

Page 17: ...e less than 35 lbs with a cable sleeve secured by the connector clamp 3 Connect the EARTH wire to the terminal marked with G The connective methods of input and output A Europe model 5KVA 7 KVA 9 KVA 11 KVA L OUTPUT INPUT T Rectifire Input 200Vac 208Vac 220Vac 230Vac 240Vac Bypass input N S R N Connect to EARTH R 11KVA 3 1 G L O U TPU T IN PU T L1 R ectifire Input 200Vac 208Vac 220Vac 230Vac 240Va...

Page 18: ...16 B US model G L1 OUTPUT INPUT L1 Rectifire Input 200Vac 208Vac 220Vac 230Vac 240Vac L2 N G L2 N Connect to EARTH ...

Page 19: ...gize When the AC input is normal press the inverter switch ON key 1 3 seconds When the AC input is failure press the switch ON key for more than 3 seconds to turn on inverter from battery The UPS starts to self test and shows the results on the back lit LCD display as show below ...

Page 20: ...NOSTIC MODE FREQ OUT XXHz DIAGNOSTIC MODE INPUT AC OK DIAGNOSTIC MODE BATTERY OK DIAGNOSTIC MODE CHARGER OK DIAGNOSTIC MODE AC DC OK DIAGNOSTIC MODE TESTING INVERTER ON LINE MODE LOAD XXX X XXKW DIAGNOSTIC MODE FREQ OUT XXHz DIAGNOSTIC MODE INPUT AC BAD DIAGNOSTIC MODE BATTERY OK DIAGNOSTIC MODE AC DC OK DIAGNOSTIC MODE TESTING INVERTER ON BATTERY LOAD XXX X XXKW CHARGER FAILURE CALL FOR SERVICE B...

Page 21: ...CT KEY ON BYPASS LOAD XXX X XXKW ON BYPASS BYPS XXXV XX XHz ON BYPASS OUT XXXV XX XHz ON BYPASS BATT XXXV XXX PRESS SELECT KEY PRESS SELECT KEY PRESS SELECT KEY PRESS SELECT KEY ON BYPASS CHRG XXXV FLOAT BOOST PRESS SELECT KEY ON BATTERY LOAD XXX X XXKW ON BATTERY IN XXXV XX XHz ON BATTERY OUT XXXV XX XHz ON BATTERY BATT XXXV XXX PRESS SELECT KEY PRESS SELECT KEY PRESS SELECT KEY PRESS SELECT KEY ...

Page 22: ...INE MODE LOAD XXX X XXKW ONLINE MODE BYPS XXXV XX XHz ONLINE MODE OUT XXXV XX XHz ONLINE MODE BATT XXXV XXX ONLINE MODE CHRG XXXV FLOAT BOOST ONLINE MODE IN S XXXV T XXXV ONLINE MODE IN R XXXV XX XHz ON BATTERY LOAD XXX X XXKW ON BATTERY BYPS XXXV XX XHz ON BATTERY OUT XXXV XX XHz ON BATTERY BATT XXXV XXX ON BATTERY CHRG XXXV OFF ON BATTERY IN S XXXV T XXXV ON BATTERY IN R XXXV XX XHz LCD FUNCTION...

Page 23: ...to set n t al Select output voltage Retrun to set n t al Select output voltage Retrun to set n t al Select output voltage Retrun to set n t al FREQUENCY 60HZ SCROLL SELECT FREQUENCY 50HZ SCROLL SELECT ECONOMY ON SCROLL SELECT ECONOMY OFF SCROLL SELECT Select output frequenci Return to set n t al Select economi mode Return to set n t al Return Return Select economi mode Return to set n t al Select ...

Page 24: ...XKW 30 seconds 150 Overload 150 Load XXX X XXKW Immediate OPERATION UNDER SHUT DOWN Condition LCD Display Message Extended Overload Shut Down Overload xxx Output Short Circuit Shut Down Short Circuit Remote Shutdown Command Shut Down Remote Command Emergency stop power off Shut Down Emergency Stop DC BUS Fault Shut Down DC BUS High Low Internal Temperature Faults Shut Down Over temperature Bypass ...

Page 25: ... maintenance In this situation AC input power is directly supplied to the load CAUTION ACTIVATE MANUAL BYPASS SWITCH ONLY WHEN UPS IS IN BYPASS MODE NORMAL STEP1 Turn off the inverter power switch To transfer UPS to bypass mode STEP 2 Turn the switch from NORMAL to BYPASS STEP 3 Turn off the AC I P breaker STEP 4 Remove the battery connects wire STEP 1 To insert the battery connect wire STEP 2 Tur...

Page 26: ... BACK UP CLOSE OPEN LOW BATTERY CLOSE CLOSE OPEN FAULT OPEN OPEN CLOSE Pin assignment FIG 5 2 Load level Battery status Battery level UPS mode Input voltage Output voltage Input frequency Temperature inside unit Set shut down delay time Enable Disable beeper Remote shut down Pin assignment Pin 2 TXD Transmit Data Pin 3 RXD Receiving Data Pin 5 GND Signal Ground Pin 7 PNP Signal Receiving DRY CONTA...

Page 27: ...remotely control and monitor UPS Contact your local dealer for more information about the optional SNMP CARD 2 1 3 4 5 6 1 2 3 4 5 6 X X 12V SNMP CHARGE L MANUAL BYPASS N N1 L1 L2 220 230 240V AC OUTPUT 200 208 50 60HZ AC INPUT 50 60HZ 220 230 240V 200 208 EPO DRY CONTACT RS 232 TORQUING SPECIFICATIONS USE COPPER CONDUCTORS ONLY REFER TO USER S MANUAL FOR DO NOT DISCONNECT EXTERNAL UNDER LOAD CAUT...

Page 28: ...P N 5011316802 ...