Chapter 4 Parameters
|
Revision July 2008, EG03, SW V1.06
4-83
Content Address
Function
35~40:
Reserved
41: GFF hardware error (HPF1)
42: CC,OC hardware error (HPF2)
43: OC hardware error (HPF3)
44: OV hardware error (HPF4)
45: U-phase error (CF3.3)
46: V-phase error (CF3.4)
47: W-phase error (CF3.5)
48: OV or LV (CF3.6)
49: Isum error (CF3.7)
50: Temperature sensor error (CF3.8)
Status of AC drive
Status monitor
Read only
2101H
Bit 0-1
00: Run LED is off and stop led is on. (AC Drive
stopping)
01: Run LED is blink and stop led is on. (AC
Drive deceleration to stop)
10: Run LED is on and stop led is blink. (AC
Drive standby)
11: Run LED is on and stop led is off. (AC Drive
running)
Bit 2
1: Jog on.
Bit 3-4
00: Rev LED is off and FWD led is on. (Forward)
01: Rev LED is blink and FWD led is on.
(Reverse to Forward)
10: Rev LED is on and FWD led is blink.
(Forward to Reverse)
11: Rev LED is on and FWD led is off. (Reverse)
Bit 5-7
Reserved
Bit 8
Master frequency source via communication
interface
Bit 9
Master frequency source via analog
Bit 10
Running command via communication interface
Bit 11
Parameter locked
Bit 12-15
Reserved
2102H
Frequency command (F)
2103H
Output frequency (H)
2104H
Output current (AXXX.X)
2105H
DC-BUS Voltage U (XXX.X)
2106H
Output voltage E (XXX.X)
2107H
Power Factor (n)
Summary of Contents for AC Motor Drive VFD-G
Page 1: ......
Page 2: ......
Page 3: ......