Chapter 7 Servo Parameters
ASDA-B2
7-66
Revision September 2013
P2-44
DPH2
Notch Filter Attenuation Rate 2
(Resonance Suppression)
Address: 0258H
0259H
Operation
Interface:
Keypad/Software
Communication
Related Section:
Section 6.3.7
Default:
0
Control
Mode:
ALL
Unit: dB
Range: 0 ~ 32
Data Size: 16-bit
Display
Format:
Decimal
Settings:
This parameter is used to set magnitude of the resonance suppression that is set by
parameter P2-43. If P2-44 is set to 0, the parameters P2-43 and P2-44 are both
disabled.
P2-45
NCF3 Notch Filter 3 (Resonance Suppression)
Address: 025AH
025BH
Operation
Interface:
Keypad/Software
Communication
Related Section:
Section 6.3.7
Default:
1000
Control
Mode:
ALL
Unit: Hz
Range: 50 ~ 2000
Data Size: 16-bit
Display
Format:
Decimal
Settings:
This parameter is used to set third resonance frequency of mechanical system. It can
be used to suppress the resonance of mechanical system and reduce the vibration of
mechanical system.
If P2-45 is set to 0, this parameter is disabled.
P2-46
DPH3
Notch Filter Attenuation Rate 3
(Resonance Suppression)
Address: 025CH
025DH
Operation
Interface:
Keypad/Software
Communication
Related Section:
Section 6.3.7
Default:
0
Control
Mode:
ALL
Unit: dB
Range: 0 ~ 32
Data Size: 16-bit
Display
Format:
Decimal