background image

Http://www.delta.com.tw/industrialautomation

 

 

 

Series Temperature Controller

 

Instruction Sheet 

 

Thank you very much for choosing Delta DTD series temperature controller. Please read this instruction sheet 
before using your DTD to ensure proper operation. Keep this instruction sheet handy for quick reference.

 

 

 

Warning

 

 

DANGER! CAUTION! ELECTRIC SHOCK!

 When the power is on, DO NOT touch the AC terminals in case 

an electric shock may occur. Make sure the power is disconnected when you check the input power

.

   

 

DTD is an OPEN-TYPE device. If it will cause serious injury to workers or damage on other equipments 
when used in a dangerous environment, please make sure it is installed in an automatic safety protection 
device.

   

 

1.

 

Always use recommended solder-less terminals: Fork terminal with isolation (M3 screw, Max. width 7.2mm). Please be 
sure to tighten them properly and make sure the wire is connected to the correct terminal.   

2.

 

Prevent dust or metallic debris from falling into the device and cause malfunctions. DO NOT modify or uninstall DTD 
series without being permitted. DO NOT use empty terminals.   

3.

 

Keep away from high-voltage and high-frequency environment during installation in case of interference. Prevent using 
the device in premises which contain:     

(a) dust or corrosive gas; (b) high humidity and high radiation; (c) shock and vibration 

4.

 

The power has to be switched off when wiring or changing temperature sensor. 

5.

 

Make sure to use compensation wire which matches the thermocouple when extending or connecting the thermocouple 
wire.  

6.

 

Use wires with resistance when extending or connecting the platinum resistance sensor. 

7.

 

Keep the wire as short as possible when wiring a sensor to the temperature controller. Separate the power cable and load 
wire in order to prevent interference and induced noise. 

8.

 

DTD is an open-type device. Make sure to install it in an enclosure which prevents dust and humidity in case of an 
electric shock.   

9.

 

Make sure the power cables and signal device are installed correctly before switching on the power; otherwise serious 
damage may occur. 

10.

 

DO NOT touch the terminals or repair the device when the power is on; otherwise an electric shock may occur. 

11.

 

Please wait for one minute after the power is switched off to allow the capacitor to discharge and DO NOT touch the 
internal wiring within this period. Use dry cloth to clean the device. DO NOT use acid or alkaline liquid to clean the 
device.

 

 

 

 

Display, LED &   

Pushbuttons

!

!

PV 

Present value/function 
display (red 7-segment LED) 

SV 

Set value 
(green 7-segment LED) 

AT 

Flashes when PID 
auto-tuning (green LED) 

OUT 

On when output (green LED) 

ALM 

On when alarm (red LED) 

 

Selecting modes 
completing setup 

 

Displaying functions 
Left-shifting the digit 

!

  Up key 

 

 

 

Ordering Information

 

!

 

DTD

0

1 2 3 4 5

 

 

Series name 

DTD: Delta D series temperature 
controller 

1 2 3 4

 

Panel size   
(W × H) 

4848: 1/16 DIN W48 × H48 mm 
4896: 1/8 DIN W48 × H96 mm 

5

 

R: Relay output SPST (250VAC, 5A) 
V: Voltage pulse output 14V +10% ~ 

-20% (Max. 40mA) 

Optional 0: 

None 

 

 

 

Specifications

 

Power input 

AC100 ~ 240V 50/60Hz 

Input power range 

85% ~ 110%, rated voltage 

Power consumption 

6VA Max. 

Display 

7-segment LED; PV in red, SV in green 

Input temperature 
sensor 

Thermocouple: K, J, T, E, N, R, S, B, U, L, 
Txk 

Platinum resistance: Pt100, JPt100 
Copper resistance: Cu50 

Analog input 

Current: 0 ~ 20mA, 4 ~ 20mA 

Voltage: 0 ~ 5V, 0 ~ 10V, 0 ~ 70mV 

Display scale 

For temperature input: K2, J2, T2, Pt100-2, JPt100 and Cu50 can display to 0.1 
degree; others display in 1degree as a unit. 

Control method 

PID, PID programmable control, On/Off, manual output 
Relay output: AC 250V, 5A, SPST 

Control output type 

Voltage pulse output: DC 14V, Max. output current 40mA 

Sampling cycle 

0.4 second (including analog input signal and sensor input signal) 

Vibration resistance 

10 ~ 55Hz 10m/s

2  

3 axes 10mins 

Shock resistance 

Max. 300m/ s

2

    3 axes 6 directions, 3 times each 

Ambient temperature 

0°C ~ 50°C 

Storage temperature 

-20°C ~ +65°C 

Operation altitude 

Less than 2,000m 

Ambient humidity 

35% ~ 85% RH (non-condensing) 

 

 

Operation Instructions on Keys

!

h

 

Switching Modes

 

DTD is in operation mode (the first level) when the power is switched on. Press 

  once to switch to the 

regulation mode (the second level), or press 

  for more than 3 seconds in operation mode to switch to the initial 

setting mode (the third level). Press 

  once in other screens to return to the operation mode. 

 

h

 

Switching Functions

 

Press 

  in each mode to select functions. Press 

  once to switch to the next function, or return to the first 

function when press 

  in the last function. 

 

h

 

Modifying Settings

 

Select the item to be set up by using 

 and 

. Next, press 

. If the item to be set up is a value, the last 

digit of the SV will flash. If you press 

  to select parameters, the SV will flash. Press 

  to increase the value 

of the digit or select parameters. When setting up the value, press 

  to left shift to the digit to be modified.   

 

h

 

Examples

 

1. DTD from STOP to RUN: Press 

  once and select parameter 

. SV will display 

. Press 

 and 

  will flash. Press 

  to save the setting and 

 will stop flashing. 

2. Modifying SV from 80 to 120: Press 

  and display 0080 (the last digit in right hand side 0 will flash). Press 

  once and 8 will flash. Next, press 

  4 times and “2” in the display 0020 will flash. Press 

 once and 

the 100s digit 0 will flash. Press 

  once and ”1” in the display 0120 will flash. Press 

  to complete and 

save the setting.

 

 

 

Input Settings

!

h

 

Setting up

 

Input Type

 

When DTD is switched on, SV will display the type of the input sensor (default K1 = thermocouple type). Press 

 

for more than 3 seconds in the operation mode and PV will display the parameter 

. Press 

  to select the 

sensor types (see the table below) and press 

  to complete and save the setting. The screen will return to the 

screen of operation mode.   

If the setting is current input, a 249

 resistor has to be connected to the current input terminals.

   

 

h

 

Setting up Input Unit

 

In the operation mode, press 

  for more than 3 seconds and PV will display the parameter 

. Press 

 

once to select the unit. If the input type is thermocouple or platinum resistance, the PV will display 

. In this 

case, press 

  to select the temperature unit (°C or °F). If the input type is an analog input, the PV will display 

. In this case, you can set up the position of the decimal point for the analog input. Press 

 to complete 

and save the setting. 

 

h

 

Setting up Input Range

 

After you complete setting up the input unit, press 

  once to display the parameter 

. Use 

 and 

 

to set the maximum value for the temperature range. Press 

  again to display the parameter 

, and use 

 and 

  to set the minimum value for the temperature range. The default range is the maximum range 

measurable (see the table below) and both parameters cannot exceed this range. When PV exceeds the range, PV 
will flash and DTD will stop its operation.   

 

When in analog input, the temperature range also refers to the maximum and minimum input values. For example, 
when 4 ~20mA input is adopted, 

 = 2,000, 

  = 400. That is to say, PV = 1,200 refers to the input is 

12mA and the unit is 0.01mA. 

 

h

 

Adjusting Input Inaccuracy

 

When there is the need to correct the measured input PV, press 

  once in the operation mode to enter the 

regulation mode. Press 

  repeatedly until the parameter of input compensation value 

 appears. 

Modifying this parameter will make the PV = measured value + input compensation value. Press 

again to 

display the parameter of input gain 

  and make PV = measured value

 

×

 

(1 + input gain/1,000) + input 

compensation value. Press 

  again and display the parameter of software filter 

  (default = 2). Increase 

this parameter to enhance the stability of the PV; however, this will result in slow reaction to the input value.   

 

Input Sensor Type 

Display 

Temperature Range 

4 ~ 20mA input 

 

-999 ~ 9,999 

0 ~ 20mA input 

 

-999 ~ 9,999 

0V ~ 10V input 

 

-999 ~ 9,999 

0V ~ 5V input 

 

-999 ~ 9,999 

0 ~ 70mV input 

 

-999 ~ 9,999 

Cu50 type 

 

-50

 o

C ~ 150

 o

C (-90.0

 o

F ~ 302.0

 o

F) 

Pt100 type 2 

 

-99.9

o

C ~ 600.0

o

C (-99.9

o

F ~ 999.9

o

F) 

Input Sensor Type 

Display 

Temperature Range 

Pt100 type 1 

 

-200

o

C ~ 600

o

C (-360

o

F ~ 1,112

o

F) 

JPt100 type 

 

-20.0

o

C ~ 400.0

o

C (-36.0

o

F ~ 752.0

o

F) 

Thermocouple TXK type 

 

-200

o

C ~ 800

o

C (-360

o

F ~ 1,472

o

F) 

Thermocouple U type 

 

-200

o

C ~ 500

o

C (-360

o

F ~ 932

o

F) 

Thermocouple L type 

 

-200

o

C ~ 850

o

C (-360

o

F ~ 1,562

o

F) 

Thermocouple B type 

 

100

o

C ~ 1,800

o

C (180

o

F ~ 3,272

o

F) 

Thermocouple S type 

 

0

o

C ~ 1,700

o

C (0

o

F ~ 3,092

o

F) 

Thermocouple R type 

 

0

o

C ~ 1,700

o

C (0

o

F ~ 3,092

o

F) 

Thermocouple N type 

 

-200

o

C ~ 1,300

o

C (-360

o

F ~ 2,372

o

F) 

Thermocouple E type 

 

0

o

C ~ 600

o

C (0

o

F ~ 1,112

o

F) 

Thermocouple T type 2 

 

-99.9

o

C ~ 400.0

o

C (-99.9

o

F ~ 752.0

o

F) 

Thermocouple T type 1 

 

-200

o

C ~ 400

o

C (-360

o

F ~ 752

o

F) 

Thermocouple J type 2 

 

-99.9

o

C ~ 999.9

o

C (-99.9

o

F ~ 999.9

o

F) 

Thermocouple J type 1 

 

-200

o

C ~ 1,200

o

C (-360

o

F ~ 2,192

o

F) 

Thermocouple K type 2 

 

-99.9

o

C ~ 999.9

o

C (-99.9

o

F ~ 999.9

o

F) 

Thermocouple K type 1 

 

-200

 o

C ~ 1,300

o

C (-360

o

F ~ 2,372

o

F) 

 

 

Control Settings

!

h

 

Setting up Control Mode

 

In the operation mode, press 

  for more than 3 seconds and PV will display the parameter 

. Press 

 

for 4 times to display the parameter 

. The default setting of this parameter is “On/Off control” 

. Use 

  to select PID control 

, PID programmable control 

 or manual control 

. Press 

 again 

and display the parameter 

  for selecting the control method. You can select heading (default) 

 or 

cooling 

. Press 

  to return to the operation mode. 

 

h

 

Setting up RUN and STOP 

 

In the operation mode, press 

  and display parameter 

. The default is RUN 

. Use 

 to select 

STOP 

. Press 

  to complete the setting and the output will be disabled. 

 

h

 

Setting up On/Off Control Parameters

 

Press 

  in the operation mode. If DTD is in On/Off heating mode, the PV will display 

; if in On/Off cooling 

mode, the PV will display 

. Modify these parameters to set up the hysteresis of On/Off. The default setting is 

0 (without hysteresis). When the output reaches SV, the control output will be disabled. When the input is bigger 
(cooling) or smaller (heating) than the SV and hysteresis, the control output will be enabled. When the On/Off 
hysteresis is not 0, the control output will be like the diagrams below.   

 

Hysteresis

HtS

OFF

ON

OFF

ON/OFF Control for Heating

SV

     

Hysteresis

CtS

OFF

ON

ON

ON/OFF Control for Cooling

SV

 

 

h

 

Setting up PID Parameters

 

When in PID control mode, you have to first decide the On/Off cycle time for the control output, i.e. the control cycle. 
Press 

  in the operation mode and PV will display 

. Press 

  5 times to display the parameters of 

heating control cycle 

  or cooling control cycle 

. Set up the cycle depending on the reaction speed of 

the control system. In principle, the faster the reaction, the shorter the cycle and more accurate the control. A short 
control cycle indicates that there will be more times of On/Off. If you adopt relay output, the short cycle will shorten 
the life span of the relay. Therefore, it is recommended that you adopt voltage output in the PID control mode. The 
default setting of the control cycle is 20 seconds.   

 

Parameters P, I and D can be set up manually or auto-tuned by DTD. Follow the steps below for the auto-tuning. 

 

Press 

  in the operation mode and PV will display the parameter 

. In RUN state 

, set the 

parameter to 

  and DTD will perform an auto-tuning. The AT indicator will flash and after the setup is 

completed, the AT indicator will be off. The PID parameters will be written in automatically and saved. 

 

To set up the parameters manually, enter the regulation mode and select the parameter 

. Press 

 

once 

to display the parameter of proportion band 

, indicating the range where P control is enabled. See the 

diagrams in the next page.

 

 

Reviews: