Parameter
and
:
can be set up when parameter
is set as “0”.
can be set up when
is not “0”.
Parameter
and
:
(control cycle for output 1) can be set up when parameter
is set as
(heating) or
(cooling) output.
(control cycle for output 2)
can be set up when parameter
is set as
(heating) or
(cooling) output.
Parameter
and
:
Can be set up when parameter
and
are set as
(heating) or
(cooling) output. (The settings in
and
have to be
different.)
For ON/OFF Control Application:
1. Set up 2 outputs: Enter parameter
and
in “initial setting mode” (see “Setting up
Parameters” section for details). Set up one of the two parameters as
or
of control
output.
2. Set up control type: Enter parameter
in “initial setting mode” (see “Setting up Parameters”
section for details) and set it up as
(ON/OFF) control.
3. Set up parameters: In “regulation mode”
Parameters
and
:
(hysteresis for output 1) can be set up when parameter
is set as
(heating)
(cooling) output.
(hysteresis for output 2) can be
set up when parameter
is set as
(heating) or
(cooling) output. You can
only set up
when
and
are set as
or
at the same time.
Parameter
:
Can be set up when parameter
and
are set as control output,
and the settings in
and
are different, e.g. output 1 is
(heating), and output
2 is
(cooling).
For Manual Control Application:
1. Set up 2 outputs: Enter parameter
and
in “initial setting mode” (see “Setting up
Parameters” section for details). Set up one of the two parameters as
or
of control
output.
2. Set up control type: Enter parameter
in “initial setting mode” (see “Setting up Parameters”
section for details) and set it up as
(manual) control.
3. Set up parameters: In “regulation mode”
Parameter
and
:
(control cycle for output 1) can be set up when parameter
is set as
(heating) or
(cooling) output.
(control cycle for output 2)
can be set up when parameter
is set as
(heating) or
(cooling) output.
Parameter
and
(in “operation mode”)
:
can be set up when parameter
is set as
(heating) or
(cooling) output.
can be set up when
parameter
is set as
(heating) or
(cooling) output.
For Programmable PID Application:
1. Set up 2 outputs: Enter parameter
and
in “initial setting mode” (see “Setting up
Parameters” section for details). Set up one of the two parameters as
or
of control
output.
2. Set up control type: Enter parameter
in “initial setting mode” (see “Setting up Parameters”
section for details) and set it up as
(programmable) control.
3. Set up parameters: In “regulation mode”
Parameter
,
and
.
Parameter
:
can be set up when parameter
is set as “0”.
Parameter
and
:
(control cycle for output 1) can be set up when parameter
is set as
(heating) or
(cooling) output.
(control cycle for output 2)
can be set up when parameter
is set as
(heating) or
(cooling) output.
Parameter
and
:
Can be set up when parameter
and
are set as
(heating) or
(cooling) output. (The settings in
and
have to be
different.)
Parameter
and
(in “operation mode")
:
Can be set up when parameter
is
set as
or
.
For Proportional Output Application:
In this application, output 1 has to be analog output.
1. Set up output function: Enter parameter
in “initial setting mode” (see “Setting up Parameters”
section for details) and set it as
(proportional) output.
2. Set
up
parameters: In “regulation mode”
Parameter
For Upper/Lower Limits of Control Output:
1. Set up upper limit: Enter parameter
in “regulation mode” (see “Setting up Parameters”
section for details). Range: Lower limit ~ 100%.
2. Set up lower limit: Enter parameter
in “regulation mode” (see “Setting up Parameters”
section for details). Range: 0 ~ upper limit %.
For Alarm Application:
1. Set up output function (only when there is group INB): Enter parameter
in “initial setting
mode” (see “Setting up Parameters” section for details) and set it as
(alarm) output.
2. Set up alarm type: Enter parameter
(with INB) or
and
(without INB) in “initial
setting mode”. See Table 2 for more details on the alarm output.
3. Set up parameters: In “operation mode”
Parameter
and
:
Can be set up when there is group INB.
Parameter
,
,
and
:
Can be set up when there is no group INB.
4. Set up delay alarm output: Enter parameter
in “regulation mode” (unit: second). The alarm
will be enabled only when the temperature reaches the alarm output condition, and the condition
remains until the delay time is reached.
DTE main unit offers 2 groups of alarm output, each with 12 alarm modes in the initial setting mode.
When SV is higher or lower than SV, the alarm output will be enabled. See the table in the next column
for the explanations on the 12 alarm output modes.
Note:
AL-H and AL-L include AL1H, AL2H and AL1L, AL2L.
SV
Alarm Mode
Alarm Output Operation
0 No
alarm
OFF
1
Alarm output is enabled when the temperature reaches upper
and lower limits: The alarm will be enabled when PV exceeds
SV + AL-H or falls below SV – A L-L.
ON
OFF
AL-L
SV
AL-H
2
Alarm output will be enabled when the temperature reaches the
upper limit: The alarm will be enabled when PV exceeds SV +
AL-H.
ON
OFF
SV
AL-H
3
Alarm output will be enabled when the temperature reaches the
lower limit: The alarm will be enabled when PV falls below SV –
A L-L.
ON
OFF
AL-L
SV
4
Alarm output will be enabled when PV is between SV + AL-H
and SV – AL-L.
ON
OFF
AL-L
SV
AL-H
5
Alarm output will be enabled when the temperature reaches the
absolute value of the upper and lower limits: The alarm will be
enabled when PV exceeds AL-H or falls below AL-L.
ON
OFF
AL-L
AL-H
6
Alarm output will be enabled when the temperature reaches the
absolute value of the upper limit: The alarm will be enabled
when PV exceeds AL-H.
ON
OFF
AL-H
7
Alarm output will be enabled when the temperature reaches the
absolute value of the lower limit: The alarm will be enabled when
PV falls below AL-L.
ON
OFF
AL-L
8
Upper/lower limit standby alarm: The alarm will be enabled when
PV reaches SV and further exceeds SV + AL-H or falls below
SV – AL –L.
ON
OFF
AL-L
AL-H
SV
9
Upper limit standby alarm: The alarm will be enabled when PV
reaches SV and further exceeds SV + AL-H.
ON
OFF
SV
AL-H
10
Lower limit standby alarm: The alarm will be enabled when PV
reaches SV and further falls below SV – AL-L.
ON
OFF
AL-L
SV
11
Upper limit hysteresis alarm: The alarm will be enabled when PV
exceeds SV + AL-H. The alarm will be disabled when PV falls
below SV.
ON
OFF
AL-L
SV
AL-H
12
Lower limit hysteresis alarm: The alarm will be enabled when PV
falls below SV – AL-L. The alarm will be disabled when PV
exceeds SV.
ON
OFF
AL-L
SV
AL-H
Table 2
Setting up Communication
1. Set
up
communication: Enter parameter
,
,
,
,
and
in “initial setting mode” (see “Setting up Parameters” section for details) and select your desired
communication settings.
2. DTE series temperature controller is able to set up or read communication settings through
DTE-2DS.
Selecting Channel
1. Select
channel: Enter parameter
in “regulation mode” (see “Setting up Parameters” section
for details) and select the channel to be monitored.
2. How does it work: DTE main unit has maximum 8 channels which can be connected to 8 input
sensors at the same time. The 8 input channels belong to group INA and INB, each group with 4
input channels. INB is optional accessory; therefore if INB is not inserted in DTE, DTE will only
show 4 channels.
Setting up Copy Function
1. Set up the function: Enter parameter
in “initial setting mode” (see “Setting up Parameters”
section for details) and select the function you desire.
2. How does it work: The copy function allows a DTE main unit to copy its parameters (including the
values set in the parameter and communication settings) to another DTE main unit through
DTE-2DS. Follow the steps below:
a. Insert DTE-2DS into the DTE main unit to be copied. Enter parameter
in “initial setting
mode” and select
, and DTE-2DS will read the parameters in the DTE main unit. Next, you
will see
on the screen, indicating that the copy is successful.
indicates the copy
fails. Press
to return to “operation mode” and you will see the present temperature value
(PV) and set temperature value (SV).
b.
Switch off DTE and withdraw DTE-2DS. Insert DTE-2DS into another DTE main unit. Enter
parameter
in “initial setting mode” and select
. DTE-2DS will write the
parameters into it. Next, you will see
on the screen, indicating that the writing-in is
successful.
indicates the writing-in fails. Press
to return to “operation mode” and
you will see the present temperature value (PV) and set temperature value (SV).
Locking the Keys on Panel
1. Lock
the
keys: Enter parameter
in “operation mode” (see “Setting up Parameters” section
for details) and select the function you desire.
2. How does it work:
indicates locking all the keys on the panel.
indicates that you can
only modify the set temperature value (SV), and all other functions are locked.
3.
Press
and
at the same time to unlock the keys.
Analog Output & Temperature Tuning
1. Set up analog output tuning: Enter parameter
and
in “regulation mode” (see
“Setting up Parameters” section for details) and tune the parameter to the desired output value.
2. Temperature
offset
tuning: Enter parameter
in “regulation mode” and tune the parameter to
the displayed temperature value.
3. How does it work:
a. Tuning analog output: For example, if you would like to have accurate 4 ~ 20mA of output, you
can set up output 0% by manual control, connect the output to ampere meter and tune
parameter
making the meter point to 4mA. Next, set up output 100% by manual control
and tune parameter
making the meter point to 20mA.
b.
Tuning temperature offset: This allows the displayed temperature to plus or minus 1 offset value.
Error Message
Error
PV
SV
Input sensor not connected
Internal communication error
Output error
Input error
Storage error
Channel disabled
Channel being initialized
How to Install
1
Remove all the terminal blocks on the panel.
2
Uncover the panel and insert DTE-2DS to the
“operation interface” slot.
3
Cover up the panel.
4
Insert the terminal blocks back to their
positions.
The content of this instruction sheet may be revised without prior notice. Please consult our distributors or
download the most updated version at http://www.delta.com.tw/industrialautomation