Warning 

 

This instruction sheet only provides introductory information on electrical specification, installation and wiring.

 

 

Switch off the power before wiring. DO NOT touch any terminal when the power is switched on.

 

 

ENA01- MOD is an OPEN-TYPE device and therefore should be installed in an enclosure free of airborne dust, 

humidity, electric shock and vibration. The enclosure should prevent non-maintenance staff from operating the 

device (e.g. key or specific tools are required to open the enclosure) in case danger and damage on the device may 

occur. 

 

 

Introduction

 

 Features 

1.  Auto-detects 10/100 Mbps transmission speed; MDI/MDI-X auto-detection. 

2.  The monitor table temporarily stores the monitored data for the user to fast save or acquire the data. 

3.  Supports MODBUS TCP protocol (supports Master and Slave mode) 

4.  Able to send out emails after being triggered. 

5.  The station address, RS-485 communication format and baud rate can be set up externally. 

6.  The communication parameters can be set up through Web. 

 Product Profile & Outline 

9

 

Unit: mm

 

 
 

1

 

Communication ports: RS-485, 
Ethernet, RS-232

 

2

 

Power indicator

 

3

 

Address setup switch

 

4

 

Data format/baud rate setup switch

 

5

 

Digit display

 

6

 

RS-485 indicator, Reset button, 
Ethernet indicator

 

7

 

Module name

 

8

 

RS-485 connector, digital input points, 
power input point, earth point

 

9

 

DIN rail connector

 

 

 

 

Specifications

 

 Ethernet Interface 

Interface 

RJ-45 with Auto MDI/MDIX 

Transmission method 

Ethernet Type II 

Transmission cable 

Category 5e, 100m (Max) 

Transmission speed 

10/100 Mbps Auto-Detection 

Network protocol 

ICMP, IP, TCP, UDP, DHCP, SMTP, MODBUS OVER TCP/IP, Delta Configuration 

ENGLISH 

 RS-485 Connector 

Interface 

RJ-11 

Transmission method 

RS-485 

Transmission speed 

110, 150, 300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200 

Communication format 

Stop bit: 1,2    Parity bit: None, Odd, Even    Data bit: 7,8    ASCII/RTU 

Communication protocol  MODBUS 

 RS-232 Connector 

Interface 

Mini Dim 

Transmission method 

RS-232 

Transmission speed 

110, 150, 300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200 

Communication format 

Stop bit: 1,2    Parity bit: None, Odd, Even    Data bit: 7,8    ASCII/RTU 

Communication protocol  MODBUS, Delta Configuration 

Transmission cable 

DVPACAB215 / DVPACAB230 / DVPACAB2A30 

 Terminal Block 

Interface 

Feed-through terminal 10PIN 

Transmission method 

RS-485 

Transmission distance 

1,200m 

Transmission speed 

110, 150, 300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200 

Communication format 

Stop bit: 1,2    Parity bit: None, Odd, Even    Data bit: 7,8    ASCII/RTU 

Communication protocol  MODBUS 

 

Electrical Specifications

 

Power voltage 

24V DC (-15% ~ 20%) supplied by feed-through terminal 

Power consumption 

3W 

Insulation voltage 

500V

 

Weight 

140g 

 

Environment

 

Noise immunity 

ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge 
EFT (IEC 61131-2, IEC 61000-4-4): Power Line:±2KV, Digital Input: ±2KV, 
Communication I/O: ±2KV 
RS (IEC 61131-2, IEC 61000-4-3): 80MHz ~ 100MHz, 10V/m. 1.4GHz ~ 2.0GHz, 
10V/m 
Conducted Susceptibility Test (EN61000-4-6, IEC61131-2 9.10): 150KHz ~ 
80MHz, 3V/m 
Surge Test (Biwave IEC61132-2, IEC61000-4-5): 
Power line 0.5KV DM, Ethernet 1KV CM, RS-485 0.5KV CM 

Operation/storage 

Operation: 0ºC ~ 55ºC (temperature), 50 ~ 95% (humidity), pollution degree 2 
Storage: -40ºC ~ 70ºC (temperature), 5 ~ 95% (humidity) 

Vibration/shock 
immunity 

International standards: IEC61131-2, IEC68-2-6 (TEST Fc)/IEC61131-2 & IEC 
68-2-27(TEST Ea) 

Certificates 

 

 

 Installation

 

 Dimension 

 

Unit: mm [inches] 

 Address Setup Switch 

Switch setting 

Content 

00 … FF 

Valid MODBUS communication address 

 

 Data Format Setup Switch 

Switch setting 

Format 

Switch setting 

Format 

7-N-1 

7-N-2 

8-N-1 

8-N-2 

7-O-1 

7-O-2 

8-O-1 

8-O-2 

7-E-1 

7-E-2 

8-E-1 

8-E-2 

 

 Baud Rate Setup Switch 

Switch setting 

Baud rate (bps) 

Switch setting 

Baud rate (bps) 

110 

4,800 

150 

9,600 

300 

19,200 

600 

38,400 

1,200 

57,600 

2,400 

115,200 

 

 

 

 

RJ-11 PIN Definition 

PIN 

Signal 

Definition 

-- 

N/C 

-- 

N/C 

D+ 

Positive pole for data 

D- 

Negative pole for data 

GND 

Ground 

-- 

N/C 

 

 

RJ-45 PIN Definition 

PIN 

Signal 

Definition 

Tx+ 

Positive pole for data transmission 

Tx- 

Negative pole for data transmission 

Rx+ 

Positive pole for data receiving 

-- 

N/C 

-- 

N/C 

Rx- 

Negative pole for data receiving 

-- 

N/C 

-- 

N/C 

 

 

RS-232 PIN Definition 

PIN 

Signal 

Definition 

-- 

N/C 

-- 

N/C 

-- 

N/C 

Rx 

Reception data 

Tx 

Transmission data 

-- 

N/C 

-- 

N/C 

GND 

Ground 

 

 Feed-through Terminal PIN Definition 

PIN 

Signal 

Definition 

SG 

Ground of signal 

D- 

Data- 

D+ 

Data+ 

X2 

Digital input 2 

X1 

Digital input 1 

X0 

Digital input 0 

S/S 

Ground of digital input 

24V 

+24V 

0V 

0V 

10 

 

Earth ground 

 

 

 

LED Indicators & Trouble-Shooting

 

There are 3 LED indicators and a digital display on ENA01-MOD. POWER indicator displays the status of the 
working power. RS-485 and LINK/ACT indicators display the connection status of the communication. The 
digital display shows the address of and errors in ENA01-MOD and the error messages from the slave. 

 

POWER LED

 

LED status 

Indication 

How to deal with it? 

Off 

Working power is abnormal 

Check if the working power of ENA01-MOD is normal. 

Green light on 

Working power is normal 

-- 

 

RS-485 LED 

LED status 

Indication 

How to deal with it? 

Off 

No communication or RS-485 
connection is abnormal. 

1. If the LED is off during the communication, check if the RS-485 in 

ENA01-MOD is normally connected. 

2. Check at least 1 node on the network is communicating normally. 

Constantly on 

Abnormal RS-485 connection 

Switch D+ and D- 

Green light 
flashes 

RS-485 connection is normal. 

-- 

 LINK/ACT LED 

LED status 

Indication 

How to deal with it? 

Off 

No power, or no network 
connection 

1. Check the power of ENA01-MOD and make sure the network 

connection is normal. 

2. Re-power ENA01-MOD. If the error still exists, send your 

ENA01-MOD back to the factory for repair. 

Green light on 

The connection is normal, but no 
data transmission. 

-- 

Green light 
flashes 

The data transmission is normal.  -- 

 Codes in Digital Display

 

Code 

Indication 

How to deal with it? 

0 ~ FF 

The node address of ENA01-MOD 
when in normal operation 

-- 

F0 

Returning to default setting 

-- 

F1 

ENA01-MOD is booting. 

-- 

F2 

Working power in low voltage 

Check if the working power is normal. 

F3 

Internal memory error 

1.  Re-power ENA01-MOD. If the error still exists, try step 2. 
2.  Reset ENA01-MOD. If the error still exists, send it back to the 

factory for repair. 

F4 

Internal error caused by 
manufacturing in the factory 

1.  Re-power ENA01-MOD. If the error still exists, try step 2. 
2.  Reset ENA01-MOD. If the error still exists, send it back to the 

factory for repair. 

F5 

Network connection error 

Check if ENA01-MOD is normally connected to the network. 

E1 

Alarm 1 triggered 

Check Alarm Input Point 1 

E2 

Alarm 2 triggered 

Check Alarm Input Point 2 

E3 

Alarm 3 triggered 

Check Alarm Input Point 3 

01 

Incorrect 

MODBUS

 function 

Check if the 

MODBUS

 instruction is correct. 

02 

Incorrect address 

Check if the 

MODBUS

 instruction is correct. 

03 

Incorrect data 

Check if the 

MODBUS

 instruction is correct. 

04 

Slave error 

1. Check if ENA01-MOD and RS-485 is connected normally. 
2. Check if the series transmission speed is consistent with that of 

other nodes on the network.

 

0B 

No response from the station 

1. Check if ENA01-MOD and RS-485 is connected normally. 
2. Check if the series transmission speed is consistent with that of 

other nodes on the network. 

 

注意事項 

 

此安裝手冊只提供電氣規格、一般規格、安裝及配線等。 

 

配線時請務必關閉電源,請勿在上電時觸摸任何端子。

 

 

本機為開放型

  (OPEN TYPE) 

機殼,因此使用者使用本機時,必須將之安裝於具防塵、防潮及免於電擊/衝

擊意外之外殼配線箱內。另必須具備保護措施(如:特殊之工具或鑰匙才可打開),防止非維護人員操作或
意外衝擊本體,造成危險及損壞。

 

 

產品簡介

 

 

功能特色

 

1.

 

自動偵測

  10/100 Mbps

傳輸速率,

MDI/MDI-X

自動偵測。

 

2.

 

提供

Monitor table

可暫存監控的資料,讓使用者快速存取。

 

3.

 

支援

MODBUS TCP 

協定

  (

支援

Master

Slave

模式

)

 

4.

 

經觸發後發送電子郵件。

 

5.

 

可由外部設定站號、

RS-485

通訊格式、鮑率。

 

6.

 

可由

Web

設定通訊參數。

 

 

產品外觀

 

1

 

通訊口

RS-485, Ethernet, RS-232

 

2

 

電源指示燈

 

3

 

站號設定開關

 

4

 

通訊格式、通訊速率設定開關

 

5

 

數位顯示器

 

6

 

RS-485

指示燈、

Reset

按鍵、

Ethernet

指示燈

 

7

 

模組名稱

 

8

 

端子台

RS-485

連接器、數位輸入點、

電源輸入、大地

 

9

 

尺寸單位:

mm

 

9

 

DIN

軌連接器

 

 

功能規格

 

 

Ethernet

連接器

 

接頭

 

RJ-45 with Auto MDI/MDIX 

傳輸方式

 

Ethernet Type II 

傳輸電纜

 

Category 5e, 100

(Max) 

傳輸速率

 

10/100 Mbps Auto-Detection 

網路協定

 

ICMP, IP, TCP, UDP, DHCP, SMTP, MODBUS OVER TCP/IP, Delta Configuration 

 

 

繁體中文 

 RS-485

連接器

 

接頭

 

RJ-11 

傳輸方式

 

RS-485 

傳輸速率

 

110, 150, 300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200 

通訊格式

 

Stop bit: 1,2    Parity bit: None, Odd, Even    Data bit: 7,8    ASCII/RTU 

通訊協定

 

MODBUS 

 

RS-232

連接器

 

接頭

 

Mini Dim 

傳輸方式

 

RS-232 

傳輸速率

 

110, 150, 300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200 

通訊格式

 

Stop bit: 1,2    Parity bit: None, Odd, Even    Data bit: 7,8    ASCII/RTU 

通訊協定

 

MODBUS, Delta Configuration 

傳輸電纜

 

DVPACAB215 / DVPACAB230 / DVPACAB2A30 

 

端子台連接器

 

接頭

 

歐式端子台

10PIN 

傳輸方式

 

RS-485 

傳輸距離

 

1,200m 

傳輸速率

 

110, 150, 300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200 

通訊格式

 

Stop bit: 1,2    Parity bit: None, Odd, Even    Data bit: 7,8    ASCII/RTU 

通訊協定

 

MODBUS 

 

電氣規格

 

電源電壓

 

24VDC (-15% ~ 20%) 

由歐式端子台輸入

 

消耗電力

 

3W 

絕緣電壓

 

500V 

重量

 

140g 

 

環境規格

 

雜訊免疫力

 

ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge 

EFT (IEC 61131-2, IEC 61000-4-4): Power Line:

±

2KV, Digital Input: 

±

2KV, 

Communication I/O: 

±

2KV 

RS (IEC 61131-2, IEC 61000-4-3): 80MHz ~ 100MHz, 10V/m. 1.4GHz ~ 2.0GHz, 10V/m 

Conducted Susceptibility Test (EN61000-4-6, IEC61131-2 9.10): 150KHz ~ 80MHz, 3V/m 

Surge Test (Biwave IEC61132-2, IEC61000-4-5): 

Power line 0.5KV DM, Ethernet 1KV CM, RS-485 0.5KV CM 

操作/儲存環境

 

操作:

0ºC ~ 55ºC

(溫度)、

50 ~ 95%

(濕度)、污染等級

  2 

儲存:

-40ºC ~ 70ºC

(溫度)、

5 ~ 95%

(濕度)

 

耐震動

/

衝擊

 

國際標準規範

IEC61131-2, IEC68-2-6 (TEST Fc) / IEC61131-2 & IEC 68-2-27(TEST Ea) 

標準

 

 

 