Modulon NH Plus Series
4-3
Table 4-1
Floor Loading for UPS
Input: 220/380 Vac / Output: 220/380 Vac
Capacity
80KVA 120KVA
Weight (Kg)
259 379
Floor Loading (kg/m
2
)
548 748
ʳ
Table 4-2
Floor Loading for External Battery Pack
ʳ
Batteries - 40 pcs
Capacity (Ah)
12V/26AH 12V/40AH
Weight (kg)
470 700
Floor Loading (kg/m
2
)
1064 1575
ʳ
4. Attach the balance supporter to the UPS with bolts.
ʳ
ʳ
Balance
Supporter
The UPS may topple over under unexpected conditions withoug balance
supporter. Be sure to mount two balance supporters on both sides of the
UPS for safety reasons.