background image

 

 

 

Warning 

 

Please read this instruction carefully before use.

 

 

Switch off the power before wiring.

 

 

DVP04AD-H2 is an OPEN-TYPE device and therefore should be installed in an enclosure free of airborne dust, 

humidity, electric shock and vibration. The enclosure should prevent non-maintenance staff from operating the device 

(e.g. key or specific tools are required to open the enclosure) in case danger and damage on the device may occur.

 

 

DO NOT connect input AC power supply to any of the I/O terminals; otherwise serious damage may occur. Check all 

the wiring again before switching on the power.

   

 

DO NOT touch any terminal when the power is switched on. DO NOT touch any internal circuit in 1 minute after the 

power is switched off.

   

 

Make sure the groud terminal 

  is correctly grounded in order to prevent electromagnetic interference.

 

 

Introduction

 

■■■■

  Model Explanation and Peripherals 

   

Thank you for choosing Delta DVP series PLC. DVP04AD-H2 is able to receive 4 points of analog input 

signals (voltage or current) and convert them into 14-bit digital signals.  Besides, through FROM/TO 

instructions in DVP-EH2 MPU program, the data in DVP04AD-H2 can be read or written. There are 49 

16-bit control registers (CR) in DVP04AD-H2. 

 

You can select voltage or current output by wiring. Range of voltage output: 

±

10V DC (resolution: 

1.25mV).  Range of current output: 

±

20mA  (resolution: 5

µ

A). 

■■■■

  Product Profile (Indicators, Terminal Block, I/O Terminals) 

 

Unit: mm 

D

 -

V

 +

I +

V

 +

2

4

V

0

V

I +

V

 +

I +

V

 +

I +

D

 +

C

O

M

8

C

H

1

C

H

2

C

H

3

C

H

4

R

S

-4

8

5

F

G

F

G

F

G

C

O

M

C

O

M

C

O

M

 

1

 

DIN rail (35mm) 

6

 

Terminals 

2

 

Connection port for extension modules 

7

 

Mounting hole 

3

 

Model name 

8

 

I/O terminals 

4

 

POWER, ERROR, A/D indicator 

9

 

Mounting port for extension modules 

5

 

DIN rail clip 

 

 

ENGLISH 

■■■■

  External Wiring 

CH1

100K

250

-10V~+10V

V+
I+

COM

CH1

100K

CH4

100K

250

-20mA~+20mA

V+
I+

COM

CH4

100K

*5

*2

AG

AG

24+
24-

DC/DC

+15V

-15V

AG

FG

FG

*3

*4

Voltageinput

Current input

Shielding cable*1

Shielding cable*1

Converter

Systemgrounding

Earth

(100 or less)

Terminal of

power module

 

*1. When performing analog input, please isolate other power wirings.   

*2. If the ripples at the loaded input terminal are too significant that causes noise interference on the wiring, connect the wiring to 0.1 

~ 0.47

µ

F 25V capacitor. 

*3.  Please connect  the 

  terminal  on  both  the  power  modules  and  DVP04AD-H2  to the  system earth  point and  ground the  system 

contact or connect it to the cover of power distribution cabinet. 

Note: 

DO NOT wire empty terminals 

.

 

 Specifications

    

Analog/Digital (4A/D) module 

Voltage input 

Current input 

Power supply voltage 

24V DC (20.4V DC ~ 28.8V DC) (-15% ~ +20%) 

Analog input channel 

4 channels/module 

Range of analog input 

±10V 

±20mA 

Range of digital conversion 

±8,000 

±4,000 

Resolution 

14 bits (1

LSB

 = 2.5mV) 

13 bits (1

LSB

 = 5

µ

A) 

Input  impedance 

0.5

 or lower 

Overall accuracy 

±

0.5% when in full scale (25°C, 77°F) 

±

1% when in full scale within the range of 0 ~ 55°C, 32 ~ 131°F 

Responding time 

3ms × the number of channels 

Isolation 

Internal circuit and analog output terminals are isolated by optical coupler. 
No isolation among analog channels. 

Range of absolute input 

±15V 

±32mA 

Digital data format 

13 significant bits out of 16 bits are available; in 2’s complement 

Average function 

Yes. Available for setting up in CR#2 ~ CR#5; range: K1 ~ K20. 

Self-diagnosis 

Upper and lower bound detection/channel 

Communication mode 
(RS-485) 

ASCII/RTU mode. Communication speed: 4,800/9,600/19,200/38,400/57,600/115,200 

bps. ASCII data format: 7-bit, even bit, 1 stop bit (7, E, 1). RTU data format: 8-bit, even 
bit, 1 stop bit (8, E, 1). RS-485 cannot be used when connected to PLC MPU. 

When connected to DVP-PLC 
MPU in series 

The modules are numbered from 0 to 7 automatically by their distance from MPU. No.0 is 

the closest to MPU and No.7 is the furthest. Maximum 8 modules are allowed to connect 
to MPU and will not occupy any digital I/O points.   

 
 

■■■■

  Other Specifications 

Power supply 

Max. rated power consumption  24V DC (20.4V DC ~ 28.8V DC) (-15% ~ +20%), 2.5W, supplied by external power. 

Environment 

Operation/storage 

Operation: 0°C ~ 55°C (temperature); 50 ~ 95% (humidity); pollution degree 2 

Storage: -25°C ~ 70°C (temperature); 5 ~ 95% (humidity) 

Vibration/shock immunity 

International standards: IEC 61131-2, IEC 68-2-6 (TEST Fc)/IEC 61131-2 & IEC 68-2-27 

(TEST Ea) 

 

Control Registers 

CR

RS-485 

parameter 

address 

Latched 

Register content 

b15 b14  b13  b12  b11  b10  b9  b8  b7  b6  b5  b4  b3  b2  b1  b0 

#0 

H’4000 

○ 

Model name 

Set up by the system. DVP04AD-H2 model code = H’6400. 

The user can read the model name from the program and see if 

the extension module exists. 

Reserved 

CH4 

CH3 

CH2 

CH1 

#1 

H’4001 

○ 

R/W  Input mode setting 

Input mode: Default = H’0000 

Mode 0: Voltage input (-10V ~ +10V) 

Mode 1: Voltage input (-6V ~ +10V) 

Mode 2: Current input (-12mA ~ +20mA) 

Mode 3: Current input (-20mA ~ +20mA) 

CR#1: The working mode of the two channels in the analog output module. There are 4 modes for each channel which 

can be set up separately. For example, if the user needs to set up CH1: mode 2 (b2 ~ b0 = 010) and CH2: mode 1 (b5 ~ 

b3 = 001), CR#1 has to be set as H000A and the higher bits (b12 ~ b15) have to be reserved. Default value = H’0000. 

#2 

H’4002 

○ 

R/W  CH1 average time 

#3 

H’4003 

○ 

R/W  CH2 average time 

#4 

H’4004 

○ 

R/W  CH3 average time 

#5 

H’4005 

○ 

R/W  CH4 average time 

Range of settings in CH1 ~ CH4: K1 ~ K20. Default = K10. 

Please note that the average time settings at CR#2 ~ CR#5 only 

need to be written in once. 

#6 

H’4006 

 

CH1 input average 

#7 

H’4007 

 

CH2 input average 

#8 

H’4008 

 

CH3 input average 

#9 

H’4009 

 

CH4 input average 

Average of input signals at CH1 ~ CH4 

CR#6 ~ CR#9: The average of the signals at CH1~CH4 obtained from the settings in CR#2~CR#5. For example, if the 

settings in CR#2~CR#5 is 10, the content in CR#6~CR#9 will be the average of the most recent 10 signals at CH1~CH4. 

#12  H’400C 

 

CH1 input present value 

#13  H’400D 

 

CH2 input present value 

#14  H’400E 

 

CH3 input present value 

#15  H’400F 

 

CH4 input present value 

Present value of input signals at CH1 ~ CH4 

#18  H’4012 

○ 

R/W 

Adjusted OFFSET value of 

CH1 

#19  H’4013 

○ 

R/W 

Adjusted OFFSET value of 

CH2 

#20  H’4014 

○ 

R/W 

Adjusted OFFSET value of 

CH3 

#21  H’4015 

○ 

R/W 

Adjusted OFFSET value of 

CH4 

OFFSET settings at CH1 ~ CH4.   

Default = K0; Unit: LSB. 

When voltage input, range: K-4,000 ~ K4,000 

When current input, range: K-4,000 ~ K4,000 

CR

RS-485 

parameter 

address 

Latched 

Register content 

b15 b14  b13  b12  b11  b10  b9  b8  b7  b6  b5  b4  b3  b2  b1  b0 

#24  H’4018 

○ 

R/W  Adjusted GAIN value of CH1 

#25  H’4019 

○ 

R/W  Adjusted GAIN value of CH2 

#26  H’401A 

○ 

R/W  Adjusted GAIN value of CH3 

#27  H’401B 

○ 

R/W  Adjusted GAIN value of CH4 

GAIN settings at CH1 ~ CH4.   

Default = K4,000; Unit: LSB. 

When voltage input, range: K-3,200 ~ K16,000 

When current input, range: K-3,200 ~ K10,400 

CR#24 ~ CR#27: The adjusted GAIN value of CH1 ~ CH4, representing the analog input voltage or current when the 

analog signal is converted into digital value 4,000. 

Note: 

GAIN value – OFFSET value = +800

LSB

 ~ +12,000

 LSB

 (voltage) or +800

 LSB

 ~ +6,400

 LSB

 (current). 

When GAIN – OFFSET is small (steep oblique), the resolution of input signal will be finer and variation on the digital value 

will be greater. When GAIN – OFFSET is big (gradual oblique), the resolution of input signal will be rougher and variation 

on the digital value will be smaller. 

#30  H’401E 

 

Error status 

Register for storing all error status.   

See the table of error status for more information. 

CR#30: Error status value (see the table below) 

Error status 

Content 

b15 ~ b8 

b7 

b6 

b5 

b4 

b3 

b2 

b1 

b0 

Abnormal power supply 

K1 (H’1) 

Incorrect mode setting 

K4 (H’4) 

OFFSET/GAIN error 

K8 (H’8) 

Hardware malfunction 

K16 (H’10) 

Abnormal digital range 

K32 (H’20) 

Incorrect average times setting 

K64 (H’40) 

Instruction error 

K128 (H’80) 

Reserved 

Note:

 Each error status is determined by the corresponding bit (b0 ~ b7) and there may be more than 2 errors occurring at the 

same time. 0 = normal; 1 = error.   

 

#31  H’401F 

○ 

R/W 

Communication address 

setting 

For setting RS-485 communication address. 

Range: 01 ~ 254. Default = K1. 

#32  H’4020 

○ 

R/W 

Communication speed (baud 

rate) setting 

For setting up communication speed: 4,800/9,600/19,200/ 

38,400/57,600/115,200 bps. ASCII data format: 7-bit, even bit, 1 

stop bit (7, E, 1). RTU data format: 8-bit, even bit, 1 stop bit (8, 

E, 1). Default = H’0002. 

b0: 4,800 bps. b1: 9,600 bps (Default). 

b2: 19,200 bps. b3: 38,400 bps.   

b4: 57,600 bps. b5: 115,200 bps 

b6 ~ b13: Reserved. 

b14: High/low bit exchange of CRC checksum (only valid in 

RTU mode). 

b15: Switch between ASCII/RTU mode; 0 = ASCII mode 

(Default). 

Reserved 

CH4 

CH3 

CH2 

CH1 

#33  H’4021 

○ 

R/W 

Returning to default setting; 

OFFSET/GAIN tuning 

authorization 

Default = H’0000. Take the setting of CH1 for example: 

1. When b0 = 0, the user is allowed to tune CR#18 (OFFSET) 

and CR#24 (GAIN) of CH1. When b0 = 1, the user is not 

allowed to tune CR#18 and CR#24 of CH1. 

2. b1 represents whether the OFFSET/GAIN tuning registers 

are latched. b1 = 0 (default, latched); b1 = 1 (non-latched)   

3. When b2 = 1, all settings will return to default values. 

CR#33: For authorizations on some internal functions, e.g. OFFSET/GAIN tuning. The latched function will store the 

output setting in the internal memory before the power is cut off. 

#34  H’4022 

○ 

Firmware version 

Displaying the current firmware version In hex; e.g. version 1.0A 

is indicated as H’010A. 

#35 ~ #48 

For system use 

Symbols: 

: Latched (when written in through RS-485 communication); 

: Non-latched; 

R: Able to read data by FROM instruction or RS-485 communication; 

W: Able to write data by TO instruction or RS-485 communication. 

LSB (Least Significant Bit):   

For voltage input: 1

LSB

 = 10V/8,000 = 1.25mV.      For current input: 1

LSB

 = 20mA/4,000 = 5

µ

A. 

CR#0 ~ CR#34: The  corresponding  parameter  addresses H’4032 ~ H’4022 are for users to read/write data by 
RS-485 communication. When using RS-485, the user has to separate the module with MPU first.   

a. Communication baud  rate: 4,800/9,600/19,200/38,400/57,600/115,200 bps. 

b. Modbus ASCII/RTU communication  protocols: ASCII data format (7-bit, even bit, 1 stop bit (7, E, 1)); RTU 

data format (8-bit, even bit, 1 stop bit (8, E, 1)). 

c. Function: H’03 (read register data); H’06 (write 1 word datum to register); H’10 (write many word data to 

register). 

d. Latched CR should be written by RS-485 communication to stay latched. CR will not be latched if written 

by MPU through TO/DTO instruction. 

 

Adjusting A/D Conversion Curve

 

Voltage  input  mode: 

CR#1 mode 0 

GAIN = 5V (4,000

LSB

). OFFSET = 0V (0

LSB

). 

CR#1 mode 1 

GAIN = 6V (4,800

LSB

). OFFSET = 2V (1,600

LSB

). 

GAIN 

The voltage input value when the digital output value = 
K4,000. 
Range: -3,200

LSB

 ~ +16,000

LSB

OFFSET 

The voltage output value when the digital input value = K0. 
Range: -4,000

LSB

 ~ +4,000

LSB

+8,000

+4,000

-4,000

10V

-8,000

-6V

-10V

6 V

2V

0

GAIN

OFFSET

D

ig

it

a

lo

u

tp

u

t

Voltage input

Mode0

Mode1

5V

 

GAIN - OFFSET 

Range: +800

LSB

 ~ +12,000

LSB

Current input mode:

 

CR#1 mode 2 

GAIN = 12mA (2,400

LSB

). OFFSET = 4mA (800

LSB

). 

CR#1 mode 3 

GAIN = 10mA (2,000

LSB

). OFFSET = 0mA (0

LSB

). 

GAIN 

The current input value when the digital output value = 
K2,000. 
Range: -3,200

LSB

 ~ +10,400

LSB

OFFSET 

The current input value when the digital output value = K0. 
Range: -4,000

LSB

 ~ +4,000

LSB

+4,000

-4,000

-12mA

-20 A

4mA

0

OFFSET

20mA

GAIN

D

ig

it

a

lo

u

tp

u

t

Current input

Mode3

Mode2

 

GAIN - OFFSET 

Range: +800

LSB

 ~ +6,400

LSB

 The user can adjust the OFFSET/GAIN curves according to the actual needs by changing the OFFSET value 

(CR#18 ~ CR#21) and GAIN value (CR#24 ~ CR#27). 

 

注意事項 

 

請在使用之前,詳細閱讀本使用說明書。

 

 

實施配線,務必關閉電源。

 

 

本機為開放型

  (OPEN TYPE) 

機殼,因此使用者使用本機時,必須將之安裝於具防塵、防潮及免於電擊

/

衝擊

意外之外殼配線箱內。另必須具備保護措施(如:特殊之工具或鑰匙才可打開)防止非維護人員操作或意外
衝擊本體,造成危險及損壞。

 

 

輸入電源不可連接於輸入

出信號端,否則可能造成嚴重的損壞,因此請在上電之前再次確認電源配線。

 

 

請勿在上電時觸摸任何端子。輸入電源切斷後,一分鐘之內,請勿觸摸內部電路。

 

 

本體上之接地端子

 

 

務必正確的接地,可提高產品抗雜訊能力。

 

 

產品簡介

 

  說明及週邊裝置 

 

謝謝您採用台達

DVP

系列產品。

DVP04AD-H2

類比信號輸入模組可接受外部

4

點類比信號輸入(電壓或

電流皆可),將之轉換成

14

位元之數位信號。透過

DVP-EH2

系列主機程式以指令

FROM/TO

來讀寫模組

內之資料,模組內具有

49

CR (Control Register) 

暫存器,每個暫存器有

16 bits

 

 

使用者可經由配線選擇電壓輸入或電流輸入。電壓輸入範圍

  ±10V DC

(解析度為

1.25mV

)。電流輸入範圍

 

±20mA

(解析度為

5

µ

A

)。

 

 

產品外觀及各部介紹 

 

尺寸單位:

mm 

D

 -

V

 +

I

 +

V

 +

2

4V

0

V

I

 +

V

 +

I +

V

 +

I

 +

D

 +

C

O
M

8

C

H

1

C

H

2

C

H

3

C

H

4

R

S

-

4

8

5

F

G

F

G

F

G

C

O

M

C

O

M

C

O
M

 

1

 

DIN

軌糟

  (35mm) 

6

  端子

 

2

  擴充機

/

擴充模組連接口

 

7

  固定孔

 

3

  機種名稱

 

8

  端子配置

 

4

  電源、錯誤及轉換指示燈

 

9

  擴充機

/

擴充模組連接座

 

5

 

DIN

軌固定扣

 

 

 

繁體中文 

 

外部配線

 

CH1

100K

250

隔離線

*1

電壓輸入

-10V~+10V

V+
I+

COM

CH1

100K

CH4

100K

250

隔離線

*1

電流輸入

-20mA~+20mA

V+
I+

COM

CH4

100K

*5

*2

AG

AG

24+
24-

接至電源模

組之

 

接地

(

100     

)

接地阻抗

以下

DC/DC

轉換器

+15 V

-15V

AG

FG

FG

*3

*4

系統接地點

 

*1

:類比輸入請與其他電源線隔離。

 

*2

:如果負載之輸入端漣波太大造成配線受雜訊干擾時,請連接

0.1 ~  0.47

µ

F 25V

之電容。

 

*3

:請將電源模組之 端及

DVP04AD-H2

類比信號輸入模組之 端連接到系統接地點,再將系統接點作接地或接到配電

箱之機殼上。

 

注意:空端子

 

 

請勿配線。

 

 

規格

 

類比

/

數位

  (4A/D) 

模組

 

電壓輸入

 

電流輸入

 

電源電壓

 

24V DC  (20.4V DC ~ 28.8V DC) (-15% ~  +20%) 

類比訊號輸入通道

 

4

通道

/

 

類比輸入範圍

 

±10V 

±20mA 

數位轉換範圍

 

±8,000 

±4,000 

解析度

 

14 bits (1

LSB

 = 2.5mV) 

13  bits (1

LSB

 = 5

µ

A) 

輸入阻抗

 

200K

以上

 

250

 

總和精密度

 

±

0.5% 

  (25°C, 77°F) 

範圍內滿刻度時。

±

1% 

  (0 ~ 55°C, 32 ~  131°F) 

範圍內滿刻度時。

 

響應時間

 

3ms × 

通道數

 

隔離方式

 

內部電路與類比區有隔離,通道間未隔離。

 

絕對輸入範圍

 

±15V 

±32mA 

數位資料格式

 

16

位元二補數,有效位

13  bits 

平均功能

 

有(

CR#2 ~ CR#5

可設定,範圍

K1 ~  K20

 

自我診斷功能

 

上下極限偵測

/

通道

 

通訊模式

  (RS-485) 

包含

ASCII/RTU

模式,通訊速率可選

  (4,800/9,600/19,200/38,400/57,600/115,200  bps)

ASCII

模式資料格式固定為

7-bit

、偶位元、

1 stop bit (7, E, 1)

RTU

模式資料格式固定為

8-bit

、偶

位元、

1 stop bit (8, E, 1)

。當與

PLC

主機串接時,

RS-485

通訊無法使用。

 

DVP-PLC

主機串接說明

 

模組編號以靠近主機之順序自動編號由

0

7

,最大可連接

8

台且不佔用數位

I/O

點數。

 

 

Reviews: