Temperature Measurement Module
Instruction Sheet
Warning
9
Please read this instruction sheet carefully before use.
9
Switch off the power before wiring.
9
DVP04PT-H2 is an OPEN-TYPE device and therefore should be installed in an enclosure free of airborne dust, humidity,
electric shock and vibration. The enclosure should prevent non-maintenance staff from operating the device (e.g. key or
specific tools are required to open the enclosure) in case danger and damages on the device may occur.
9
DO NOT connect input AC power supply to any of the I/O terminals; otherwise serious damage may occur. Check all the
wiring again before switching on the power.
9
Do NOT touch any terminal when the power is switched on.
9
Make sure the ground termnial
is correctly grounded in order to prevent electromagnetic interference.
9
Use wires with resistance when connect the platinum resistance thermister (RTD) to PLC.
9
Keep the wire as short as possible between RTD and PLC and the power wire as far away as possible from I/O wire to
prevent interference.
Introduction
1.1 Model Explanation & Peripherals
Thank you for choosing Delta’s DVP series. DVP04PT-H2 is able to receive 4 points of platinum temperature
sensors (PT100 3-WIRE 100
Ω
3850 PPM/
°
C (DIN 43760 JIS C1604-1989)) and convert them into 14-bit digital
signals. Besides, through FROM/TO instructions in DVP-EH2 MPU program, DVP04PT-H2 is able to read and
write the data in the module. There are 49 16-bit control registers (CR) in DVP04PT-H2.
DVP04PT-H2 displays temperatures in Celsius (resolution: 0.1°C) and Fahrenheit (resolution: 0.18°F).
Nameplate Explanation
04 PT-H20 T6 500 001
VX.XX
24Vdc 2.5W
MADE IN XXXXX X
D e l t a P L C m o d e l n a m e
14 BITS
PT100
B a r c o d e , s e r i a l N o . , Ve r s i o n
P o w e r i n p u t s p e c i f i c a t i o n
A n a l o g I / O m o d u l e s p e c i f i c a t i o n
Model/Serial No. Explanation
DVP series
AD: Analog input
DA: Analog output
PT: Temperature measurement (PT-100)
TC: Temperature measurement
(thermocouple)
Points (input + output)
Model type
XA: Mixed analog I/O
HC: High-speed counter input
PU: Single-axis position control
H: For EH series MPU
H2: For EH2 series MPU
Model name
Production No.
Production week
Production year (2006)
Production plant (Taoyuan)
Version No.
1.2 Product Profile (Indicators, Terminal Block, I//O Terminals)
Unit: mm
D
-
L
+
L
-
L
+
24V
0V
L
-
L
+
L
-
L
+
L
-
D +
I -
8
CH
1
C
H
2
CH
3
C
H
4
RS
-4
8
5
F
G
I -
F
G
I -
F
G
I -
1
DIN rail (35mm)
6
Terminals
2
Connection port for extension unit/module
7
Mounting hole
3
Model name
8
I/O terminals
4
POWER, ERROR, A/D indicator
9
Mounting port for extension unit/module
5
DIN rail clip
1.3 External
Wiring
PT100
CH1
CH4
1mA
DC/DC
5V
AG
+15V
-15V
AG
AG
AG
24+
0V
FG
I-
L-
L+
FG
I-
L-
L+
*2
*3
1mA
Shielding
cable *1
Shielding
cable *1
Terminal of
power module
Converter
System
grounding
Earth
(100 or less)
PT100
*1: Wiring for analog input should adopt cables of PT100 temperature sensor or double shielding cable and should be
separated from other power cables that may cause interference. Please use 3 wires for PT100.
*2: Terminal FG is the ground location for noise suppression.
*3: Please connect the
terminal on both the power module and DVP04PT-H2 to the system earth point and ground the
system contact or connect it to the cover of power distribution cabinet.
Note: DO NOT wire empty terminal
.
Specifications
2.1. Functions
Temperature measurement
(04PT) module
Celsius (°C)
Fahrenheit (°F)
Power supply voltage
24 VDC (20.4VDC ~ 28.8VDC) (-15% ~ +20%)
Analog output channel
4 channels/module
Applicable sensor
types
3-WIRE PT100
Ω
3850 PPM/°C (DIN 43760 JIS C1604-1989)
Current excitation
1mA
Range of input
temperature
-200 ~ 600
-328 ~ 1112
Range of digital
conversion
K-2,000 ~ K6,000
K-3,280 ~ K11,120
Resolution
14 bits (0.1)
14 bits (0.18)
Output impedance
0.5
Ω
or less
Overall accuracy
±
0.5% when in full scale (25°C, 77°F)
±
1% when in full scale within the range of 0 ~ 55°C, 32 ~ 131°F
Response time
200 ms × the number of channels
Isolation
Isolation between digital area and analog area. No isolation among channels.
Digital data format
13 significant bits out of 16 bits are available; in 2’s complement.
Average function
Yes; available for setting up in CR#2 ~ CR#5; range: K1 ~ K20
Self-diagnosis
Upper and lower bound detection/channel
Protection
The voltage output is protected by short circuit. Please also be aware that being short
circuit for too long period of time may cause damage on internal circuit. The current
output can be open circuit.
Communication mode
(RS-485)
ASCII/RTU mode.
Communication speed: 4,800/9,600/19,200/38,400/57,600 /115,200 bps
ASCII data format: 7-bit, Even bit, 1 stop bit (7, E, 1)
RTU data format: 8-bit, Even bit, 1 stop bit (8, E, 1)
RS-485 cannot be used when connected to PLC MPU.
When connected to
DVP-PLC MPU in
series
The modules are numbered from 0 to 7 automatically by their distance from MPU. No.
0 is the closest to MPU and No. 7 is the furthest. Maximum 8 modules are allowed to
connect to MPU and will not occupy any digital I/O points.
2.2. Others
Power Supply
Max. rated power
consumption
24 VDC (20.4VDC ~ 28.8VDC) (-15% ~ +20%), 2.5W supplied by external power
Environment
Operation/storage
Operation: 0°C ~ 55°C (temperature); 50 ~ 95% (humidity); pollution degree 2
Storage: -40°C ~ 70°C (temperature); 5 ~ 95% (humidity)
Vibration/shock
immunity
International standard: IEC1131-2, IEC 68-2-6 (TEST Fc)/IEC1131-2 & IEC 68-2-27
(TEST Ea)
Control Registers
DVP04PT-H2
Description
CR
#
RS-485
Parameter
address
Latched
Register content
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
#0
H’4064
○
R
Model name
Set up by the system. DVP04PT-H2 = H’6402
#1
Reserved
#2
H’4066
○
R/W CH1 average time
#3
H’4067
○
R/W CH2 average time
#4
H’4068
○
R/W CH3 average time
#5
H’4069
○
R/W CH4 average time
Range of settings in CH1 ~ CH4: K1 ~ K20
Default = K10
#6
H’406A
╳
R
Average °C temp.
measured at CH1
#7
H’406B
╳
R
Average °C temp.
measured at CH2
#8
H’406C
╳
R
Average °C temp.
measured at CH3
#9
H’406D
╳
R
Average °C temp.
measured at CH4
Average Celsius temperature measured at CH1 ~ CH4.
Unit: 0.1°C
#10 ~ #11
Reserved
#12 H’4070
╳
R
Average °F temp.
measured at CH1
#13 H’4071
╳
R
Average °F temp.
measured at CH2
#14 H’4072
╳
R
Average °F temp.
measured at CH3
#15 H’4073
╳
R
Average °F temp.
measured at CH4
Average Fahrenheit temperature measured at CH1 ~ CH4.
Unit: 0.1°F
#16 ~ #17
Reserved
#18 H’4076
╳
R
Present °C temp.
measured at CH1
#19 H’4077
╳
R
Present °C temp.
measured at CH2
#20 H’4078
╳
R
Present °C temp.
measured at CH3
#21 H’4079
╳
R
Present °C temp.
measured at CH4
Present Celsius temperature measured at CH1 ~ CH4.
Unit: 0.1°C
#22 ~ #23
Reserved
#24 H’407C
╳
R
Present °F temp.
measured at CH1
#25 H’407D
╳
R
Present °F temp.
measured at CH2
#26 H’407E
╳
R
Present °F temp.
measured at CH3
#27 H’407F
╳
R
Present °F temp.
measured at CH4
Present Fahrenheit temperature measured at CH1 ~ CH4.
Unit: 0.1°F
#28 ~ #29
Reserved
#30 H’4082
╳
R
Error status
Register for storing all error status. See the table of error status for more
information.
#31 H’4083
○
R/W Communication address
setting
For setting RS-485 communication address. Range: 01 ~ 255
Default = K1
#32 H’4084
○
R/W
Communication speed
(Baud Rate) setting
For setting up communication speed:
4,800/9,600/19,200/38,400/57,600/115,200 bps
ASCII data format: 7-bit, Even bit, 1 stop bit (7, E, 1)
RTU data format: 8-bit, Even bit, 1 stop bit (8, E, 1) Default = H’0002
b0: 4,800 bps b1: 9,600 bps (default)
b2: 19,200 bps b3: 38,400 bps
b4: 57,600 bps b5: 115,200 bps
b6 ~ b13: reserved
b14: High/low bit exchange of CRC checksum (only valid in RTU mode)
b15: Switch between ASCII/RTU modes; 0 = ASCII mode (default)
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
ERR LED
CH4
CH3
CH2
CH1
#33 H’4085
○
R/W
Returning to default
setting
Take the setting of CH1 for example:
1. b0 is reserved.
2. b1 is reserved.
3. When b2 is set as 1, all the settings will return to default settings.
ERR LED definition: default of b12 ~ b15 = 1111
1. b12 corresponds to CH1. When b12 = 1 or the scale exceeds the range,
ERR LED will flash.
2. b13 corresponds to CH2. When b13 = 1 or the scale exceeds the range,
ERR LED will flash.
3. b14 corresponds to CH3. When b14 = 1 or the scale exceeds the range,
ERR LED will flash.
4. b15 corresponds to CH4. When b15 = 1 or the scale exceeds the range,
ERR LED will flash.
#34 H’4086
○
R
Firmware version
Displaying the current firmware version in hex; e.g. version 1.0A is indicated
as H’010A
#35 ~ #48
For system use
Symbols
○
: latched (when written in through RS-485 communication)
╳
:
non-latched
R: Able to read data by FROM instruction or RS-485 communication
W: Able to write data by TO instruction or RS-485 communication
Explanations:
1. CR#0: Model name. The user can read the model name from the program and see if the extension module
exists.