Chapter 4 Parameter Settings
|
DD Series
4-45
Encoder Feedback Fault Treatment (PGF1, PGF2)
Control mode
VFPG
FOCPG
Factory setting: 2
Settings
0: Warn and keep operation
1: Warn and ramp to stop
2: Warn and stop operation
Detection Time for Encoder Feedback Fault
Control mode
VFPG
FOCPG
FOCPM
Factory setting: 1.0
Settings 0.0~10.0sec
When PG loss, encoder signal error, pulse signal setting error or signal error, if time exceeds the
detection time for encoder feedback fault (Pr.03-04), the PG signal error will occur. Refer to the Pr.03-03
for encoder feedback fault treatment.
Encoder Stall Level (PGF3)
Control mode
VFPG
SVC
FOCPG
FOCPM
Factory setting: 115
Settings 0~120% (0: disable)
This parameter determines the maximum encoder feedback signal allowed before a fault occurs. (max.
output frequency Pr.01-31 =100%)
Encoder Stall Detection Time
Control mode
VFPG
SVC
FOCPG
FOCPM
Factory setting: 0.1
Settings 0.0
~
2.0sec
Encoder feedback error (Max. output frequency Pr.01-31=100%)
Encoder Slip Range (PGF4)
Control mode
VFPG
SVC
FOCPG
FOCPM
Factory setting: 50
Settings 0~50%
(0:disable)
Encoder feedback error (Max. output frequency Pr.01-31=100%)
Encoder Slip Detection Time
Control mode
VFPG
SVC
FOCPG
FOCPM
Factory setting: 0.5
Settings 0.0
~
10.0sec
Encoder feedback error (Max. output frequency Pr.01-31=100%)
Encoder Stall and Slip Error Treatment
Control mode
VFPG
SVC
FOCPG
Factory setting: 2
Settings Encoder PG signal feedback error (Max. output frequency Pr.01-31=100%)
0: Warn and keep operation
1: Warn and ramp to stop
2: Warn and coast to stop
When the value of (rotation speed – motor frequency) exceeds Pr.03-07 setting, detection time exceeds
Pr.03-08 or motor frequency exceeds Pr.03-05 setting, it will start to accumulate time. If detection time
exceeds Pr.10-06, the encoder feedback signal error will occur. Refer to Pr.03-09 encoder stall and slip
error treatment.
Door Width Auto-tuning Frequency
Control mode
VF
VFPG
SVC
FOCPG
FOCPM
Factory setting: 5.0
Settings 0.10~120.00Hz
This parameter is the frequency of motor when using door width auto-tuning function.
D
oor Width Auto-tuning
Control mode
VF
VFPG
SVC
FOCPG
FOCPM
Factory setting: 0
Summary of Contents for VFD-DD Series
Page 1: ......
Page 13: ...Chapter 1 Introduction DD Series 1 7 ECMD B9160GMS...