Chapter 4 Parameter Settings
|
DD Series
4-49
Within the holding time, when CD command (door close command) is given, the drive will begin door
close action.
When Pr.04-18 set to 999.9, OD terminal is executing a permanent holding command, user can only
terminate this command by using the STOP/RESET key on digital keypad.
Door Open Acceleration Time of S1 Curve
Control mode
VF
VFPG
SVC
FOCPG
FOCPM
Factory setting: 0.0
Settings 0.0~10.0sec
Door Open Acceleration Time of S2 Curve
Control mode
VF
VFPG
SVC
FOCPG
FOCPM
Factory setting: 0.0
Settings 0.0~10.0sec
This parameter is used to ensure smooth acceleration and deceleration via S-curve, different setting will
create different S-curve. When this function is activated, the drive will create a smooth acceleration and
deceleration curve by original acceleration and deceleration time. Setting Pr.04-19=0.0 or Pr.04-20=0.0
will create a linear acceleration and deceleration curve.
Actual acceleration time = the selected acceleration time for door open + (Pr.04.19 + Pr.04.20)/2
04.19=S1
04.20=S2
04.08
Accerleration
Time
Freqeuncy
Door Open DC Brake Current Level
Control mode
VF
VFPG
SVC
Factory setting: 0
Settings 0~100%
This parameter sets the level of DC Brake Current output to the motor during start-up and stopping.
When setting DC Brake Current, the Rated Current (Pr.00-01) is regarded as 100%. It is recommended
to start with a low DC Brake Current Level and then increase until proper holding torque has been
attained. Do not set Pr.04-21 greater than rated current in order to prevent motor damage. Also for your
personal safety, do not use DC braking for door holding action.
When AC motor drive is in FOCPG/FOCPM control mode, DC brake functions are ready to use, no
additional setting is required.
Door Open DC Brake Time when Startup
Control mode
VF
VFPG
SVC
FOCPG
FOCPM
Factory setting: 0.0
Settings 0.0~60.0sec
This parameter determines the duration of the DC Brake current after a RUN command.
Door Open DC Brake Time when Stopping
Control mode
VF
VFPG
SVC
FOCPG
FOCPM
Factory setting: 0.0
Settings 0.0~60.0sec
This parameter determines the duration of the DC Brake current during braking.
Summary of Contents for VFD-DD Series
Page 1: ......
Page 13: ...Chapter 1 Introduction DD Series 1 7 ECMD B9160GMS...