background image

INSTALLATION 

 

SM6000 

13 / 21 

DELTA ELEKTRONIKA B.V. 

rev. Nov. 2020 

 

 

4

 

INSTALLATION 

 

Warning!

 carefully read the chapter "Safety Instructions" in 

this manual before connecting or operating the unit! 

4.1

 

HUMIDITY & CONDENSATION 

 

During normal operation, humidity will not harm the power 
supply, provided the air is not aggressive. The heat normally 
produced in the power supply will keep it dry. 

 

Avoid condensation inside the power supply, to prevent 
break-down. Condensation can occur during a period the 
power supply has been switched off (or operating at no load) 
and the ambient temperature is increasing. Always allow the 
power supply to dry before switching it on again. 

4.2

 

TEMPERATURE & COOLING 

 

The storage temperature range is 

–40 to +85 °C. 

 

The operating temperature range at full load is 

–20 to +50 °C. 

 

This temperature range only holds when the air-intakes and 
air-outlets are unobstructed and the temperature of the air-
intake is not higher than +50 °C. 

 

When the power supply is mounted in a cabinet, please note 
that the temperature of the air-intake should be kept low and 
avoid a short circuit in the airflow i.e. the hot air leaving the 
air-outlets entering the air-intakes again. 

 

Please note: a lower temperature extends the lifetime of the 
power supply. 

4.3

 

19" RACK MOUNTING 

 

On both sides in the rack, mount a proper support slide that 
can hold the weight of the unit. It is advised to use a separate 
slide for each unit. 

 

After placing the unit on the slide, add all 4 screws to mount 
the front panel of the power supply to the vertical rack posts. 
Use proper screws intended for keeping equipment of this 
weight in position. 

 

Assuming the rack is deliberately designed for the weight, 
stacking of the units is allowed without limitations. See 
previous paragraph for cooling instructions. 

4.4

 

OPERATING THE UNIT FOR THE FIRST TIME  

 

Check there is no condensation on the unit. If there is, allow 
some time to dry. 

 

Check there is a link b and S+ and between 

– and 

S

– on the SENSE BLOCK (on rear panel). 

 

Check there is a link between pins of the Interlock (CON A).  

 

Set the CV and CC potentiometers to minimum (fully anti 
clockwise). For units with Option P220, this is not needed. 
These units are set to start at 0 V - 0 A when operated for the 
first time. 

 

For the mains power, connect a cable of 4-wires of 2.5mm

2

Use a torque of 0.6Nm to fasten the screws on the AC input 
connector. 

 

For the DC output power, see table 4 - 1 for cable diameters 
and mounting torque. 

 

For 

high DC current

 make sure to use low resistive 

connections between the power supply and the load: 

- Mount the cable lugs directly on the DC output strips  
  followed by a washer, split washer and a nut (see fig. 4 - 1). 
  Always in this order! 
- Never place washers between the lugs and the strips 
  because this can result in excessive heat! 
- Only use nuts and washers supplied with the unit. 

 

Switch on unit. 

 

Disable the Keylock function, see next paragraph. 

 

Check the unit is not in Remote CV or Remote CC (LED’s for 
this function should be off). Press the REMOTE/LOCAL 
button until both LED’s are off. 

 

Turn on DC output by pressing the OUTPUT ON/OFF button. 

 

Turn both the CV and CC potentiometer a few turns 
clockwise.  

 

A voltage should now be present on the output. 

 

By pressing the DISPLAY CV/CC SETTING button the meters 

 

 

 

fig 4 - 1 

Low resistive cable connection by mounting the 

cables directly on the DC output strips. 

Unit 

DC Output 

cable [mm

2

Bolts 

Torque 

[Nm] 

SM15-400 

150 

M12 

80 

SM30-200 

70 

M10 

40 

SM45-140 

35 

M10 

40 

SM60-100 

35 

M10 

40 

SM70-90 

25 

M10 

40 

SM120-50 

10 

M8 

20 

SM300-20 

M8 

20 

SM600-10 

2.5 

M8 

20 

 

table 4 -1  

Recommended cable diameters and mounting torque.  

Summary of Contents for SM 120-50

Page 1: ...50 SM300 20 SM600 10 PRODUCT MANUAL Contents 1 Safety Instructions 2 Sicherheitshinweise 3 General 4 Installation 5 Trouble Shooting 6 Maintenance Calibration 7 EU Declaration of Conformity Product Manuals and Driver Example Software For several Applications build in Options and Interfaces there are Application Notes separate Product Manuals and Driver Example Software available on available on ou...

Page 2: ...red safe DC power terminals and sense connections programming monitor status signals Interlock Master Slave connections ACF DCF relay all Delta Elektronika interfaces Caution 1 If a low voltage unit has both DC power terminals floating or if the DC terminals are in series with an external high AC or DC voltage the minus DC power terminal can exceed the safe value in respect to ground as specified ...

Page 3: ...ch off the unit Disconnect the unit from the AC mains supply and from the DC power application Wait for 5 minutes to allow internal capacitors to discharge Unscrew the screws and remove the cover s Always place the cover s back before connecting the unit to the mains supply again 1 12 Environmental Conditions The Delta Elektronika power supplies safety approval applies to the following operating c...

Page 4: ...rammierung Monitor Status Signale InterLock Master Slave Anschlüsse ACF DCF Relais Schnittstellen mit Funktionale Isolation Schnittstellen ohne Sicherheitsisolation Vorsicht 1 Falls beide DC Anschlussklemmen eines Niederspannungsgerätes potentialfrei sind oder falls die DC Klemmen in Reihe mit einer externen AC oder DC Hochspannung geschaltet sind kann die minus DC Anschlussklemme den sicheren Wer...

Page 5: ...ungsbedingungen Die Stromversorgungssicherheitszulassung von Delta Elektronika gilt für die folgenden Betriebsbedingungen Innengebrauch Umgebungstemperatur 20 bis 50 C Maximale relative Luftfeuchtigkeit 95 nicht kondensierend bis zu 40 C 75 nicht kondensierend bis zu 50 C Höhe bis zu 2000 m Verschmutzungsgrad 2 Diese Kennzeichnung auf dem Produkt seiner Verpackung oder seiner Literatur weist darau...

Page 6: ...and the harmonic distortion of the AC input current will be relatively low The peak inrush current is electronically limited Switching on and off repeatedly will not result in excessive currents like with NTC circuits 3 4 STANDBY AC INPUT POWER The unit consumes very little power when in standby This makes it possible to leave the AC input power on when the output is disabled using the Output On O...

Page 7: ... by the computer 3 12 MONITORING OUTPUTS The monitor outputs give a voltage 0 5 V proportional to the output current or voltage The output current can easily be measured using the I monitor see fig 3 6 The monitor outputs are buffered with op amp s and protected with series resistors and parallel zener diodes see fig 3 7 The table in fig 3 5 shows the impedance levels of the monitoring outputs For...

Page 8: ...to the ACF relay see fig 3 10 fig 3 10 Status relay outputs on CON D This situation gives the relay positions during fault condition fig 3 8 Location of output terminals and analog programming connector on the rear panel CON A Interlock Connector CON B Master connector for Master Slave operation output CON C Slave connector for Master Slave operation input CON D Relay Outputs contacts 1 6 CON E An...

Page 9: ... the rise and fall time is 5 to 25 times faster see datasheet The programming source must be floating or otherwise an ISO AMP CARD must be used a non floating source will result in slope distortion When using hi speed programming it is generally not recommended to use remote sensing or serial parallel operation Consult factory for advice Note that the output ripple is higher 3 20 PULSATING LOAD To...

Page 10: ...ld up time see fig 3 17 3 26 TURN ON DELAY The DC output voltage is available about 0 2 sec after mains switch on 3 27 AC INRUSH CURRENT The inrush current is electronically limited Repeatedly switching on and off does not change the maximum peak current Switching on and off at a fast rate can overheat the inrush current limiter With the result that the unit does not start anymore After cooling do...

Page 11: ...llel operation in combination with Power Sink option only one unit can have a Power Sink Refer to Power Sink manual for details and restrictions 3 32 MASTER SLAVE OPERATION The Master Slave feature makes it possible to use power supplies as building blocks to form one large unit fig 3 20 Mixed parallel series operation is also possible to a maximum of 600 V The resulting combination of units behav...

Page 12: ...ons such as variable coarse fine pitch adjustment locking of CV CC settings and a selectable start up voltage start at 0V 0A or at last settings The lower voltage units have analog potentiometers for the CV CC controls Optional they can be equipped with screwdriver adjustment for CV CC settings at the front panel or also with digital encoders option P220 See fig 3 23 for option P001 3 35 COOLING T...

Page 13: ...ts is allowed without limitations See previous paragraph for cooling instructions 4 4 OPERATING THE UNIT FOR THE FIRST TIME Check there is no condensation on the unit If there is allow some time to dry Check there is a link between and S and between and S on the SENSE BLOCK on rear panel Check there is a link between pins of the Interlock CON A Set the CV and CC potentiometers to minimum fully ant...

Page 14: ...ion UP the settings after mains switch on will be the same as before switching the mains voltage off 4 7 ANALOG PROGRAMMING Set DIP switch 1 of SW1 in position UP to select CON E for programming For SM300 20 SM600 10 see paragraph ISO AMP Disable Keylock Set the unit in REMOTE CV for voltage programming and or in REMOTE CC for current programming Use the REMOTE LOCAL button and push this button se...

Page 15: ...o S and S See fig 4 5 and fig 4 6 With remote sensing the voltage on the load can be kept constant The voltage drop in the load leads will be compensated This feature is not recommended for normal use because it can easily give problems Max 2 V per load lead can be compensated Note that the voltage drop in the leads decreases the max output voltage rating In fig 4 7 it can be seen that on a 15 V p...

Page 16: ...aster via CON B and CON C use standard UTP cables RJ45 On all units put DIP switch 4 of SW1 in position DOWN to set the units in M S series mode After turning the units on again the slaves will be in Remote CV mode and the Keylock see previous paragraph is activated This is because the unit automatically detects the presence of the RJ45 connector in CON C if this cable is connected to another unit...

Page 17: ...o each other to have a low inductance Not following these instructions can cause instability The S and S could be connected to the load if desired but this is not recommended because of the complexity and possible instability 4 17 PARALLEL OPERATION OF FAST PROGRAMMING VERSIONS Master Slave operation is not recommended Normal parallel operation can give problems each combination has to be tested f...

Page 18: ...emote CV and or Remote CC LED should be on The unit works OK in manual control but in programming mode the output voltage current has a large error Probably the fuse in series with Ø pin 1 of programming connector tripped the fuse F27_1 650 mA is a self resetting type see fig 5 1 To check the fuse F27_1 measure the voltage between Ø and the minus output during the fault condition The voltage shoul...

Page 19: ... because of a bad connection Disconnect the mains wait a few minutes and try again Note the following As soon as the ACF LED is on the settings for Remote CV Remote CC and Keylock will be saved If the unit turns back on it will have the same settings For the setting of Output On Off after turning the unit back on the position of DIP switch 2 on SW1 is determining If the ACF situation lasts a few s...

Page 20: ...brated and normally need no further calibration After installation of a new or different interface no calibration is needed Only in special situations for example after repairing a unit calibration can be necessary 6 5 METER CALIBRATION DIGITAL METERS The full scale indication can be calibrated with R25_31 and R25_36 on P596 see fig 6 2 6 6 SPECIAL CALIBRATIONS The following calibrations must be d...

Page 21: ...e official Journal of the European Communities EN 61000 6 3 2007 Generic Emissions residential light industrial A1 2011 EN 61000 3 2 2014 Power Harmonics EN 61000 3 3 2013 Voltage fluctuation and flicker EN 61000 6 1 2007 Generic Immunity residential light industrial EN 61000 6 2 2005 Generic Immunity industrial environment EN 60950 1 2006 Safety of IT equipment A1 2010 A11 2009 A12 2011 A2 2013 E...

Reviews: