- 62 -
Address Type
Input Register description
AP ED RE AL
51 B
Alarm for temperature with NTC10K sensor of channel 3:
0=OFF, 1=lower threshold alarm, 2=higher threshold alarm.
9
56 SW
D
IFFERENTIAL
P
RESSURE
for the range
r3
in the set measurement
unit (the multiplier depends on the set unit).
9
57 B
Differential pressure alarm for the range r3:
0=OFF, 1=lower threshold alarm, 2=higher threshold alarm.
9
60 SW
D
IFFERENTIAL
P
RESSURE
for ranges
r1
and
r2
in the set meas-
urement unit (the multiplier depends on the set unit).
9
61 B
Differential pressure alarm for ranges r1 and r2:
0=OFF, 1=lower threshold alarm, 2=higher threshold alarm.
9
62 SW
D
IFFERENTIAL
P
RESSURE
for the range
r4
in the set measurement
unit (the multiplier depends on the set unit).
9
63 B
Differential pressure alarm for the range r4:
0=OFF, 1=lower threshold alarm, 2=higher threshold alarm.
9
64 SW
T
EMPERATURE
with
Pt100 sensor
of HP3517E… probe in the set
measurement unit (x10).
9
65 B
Alarm for temperature with Pt100 sensor
of HP3517E… probe:
0=OFF, 1=lower threshold alarm, 2=higher threshold alarm.
9
68 SW
UVA
IRRADIANCE
in mW/m
2
.
9
69 B
UVA irradiance alarm:
0=OFF, 1=lower threshold alarm, 2=higher threshold alarm.
9
70 SW
P
ROPORTION OF
UV
PRESENT
in µW/lumen.
9
71 B
Proportion of UV present alarm:
0=OFF, 1=lower threshold alarm, 2=higher threshold alarm.
9
Measured values and status of measurement alarms for configurable inputs
1000 +
200
x
(
N
-1) SW
T
EMPERATURE
with 2-wire
Pt100 sensor
of channel
N
in the set
measurement unit (x10).
9
1001 +
200
x
(
N
-1)
B
Alarm for temperature with 2-wire Pt100 sensor
of channel
N
:
0=OFF, 1=lower threshold alarm, 2=higher threshold alarm.
9
1002 +
200
x
(
N
-1) SW
T
EMPERATURE
with 3-wire
Pt100 sensor
of channel
N
in the set
measurement unit (x10).
9
1003 +
200
x
(
N
-1)
B
Alarm for temperature with 3-wire Pt100 sensor
of channel
N
:
0=OFF, 1=lower threshold alarm, 2=higher threshold alarm.
9
1004 +
200
x
(
N
-1) SW
T
EMPERATURE
with 4-wire
Pt100 sensor
of channel
N
in the set
measurement unit (x10).
9
1005 +
200
x
(
N
-1)
B
Alarm for temperature with 4-wire Pt100 sensor
of channel
N
:
0=OFF, 1=lower threshold alarm, 2=higher threshold alarm.
9
1006 +
200
x
(
N
-1) SW
T
EMPERATURE
with 2-wire
Pt1000 sensor
of channel
N
in the set
measurement unit (x10).
9
1007 +
200
x
(
N
-1)
B
Alarm for temperature with 2-wire Pt1000 sensor
of channel
N
:
0=OFF, 1=lower threshold alarm, 2=higher threshold alarm.
9
1008 +
200
x
(
N
-1) SW
T
EMPERATURE
with 3-wire
Pt1000 sensor
of channel
N
in the set
measurement unit (x10).
9
1009 +
200
x
(
N
-1)
B
Alarm for temperature with 3-wire Pt1000 sensor
of channel
N
:
0=OFF, 1=lower threshold alarm, 2=higher threshold alarm.
9
1010 +
200
x
(
N
-1) SW
T
EMPERATURE
with 4-wire
Pt1000 sensor
of channel
N
in the set
measurement unit (x10).
9
1011 +
200
x
(
N
-1)
B
Alarm for temperature with 4-wire Pt1000 sensor
of channel
N
:
0=OFF, 1=lower threshold alarm, 2=higher threshold alarm.
9
1012 +
200
x
(
N
-1) SW
T
EMPERATURE
with
TC_K
sensor of channel
N
in the set
measurement unit (x10).
9
1013 +
200
x
(
N
-1)
B
Alarm for temperature with TC_K sensor
of channel
N
:
0=OFF, 1=lower threshold alarm, 2=higher threshold alarm.
9
1014 +
200
x
(
N
-1) SW
T
EMPERATURE
with
TC_J
sensor
of channel
N
in the set
measurement unit (x10).
9
1015 +
200
x
(
N
-1)
B
Alarm for temperature with TC_J sensor
of channel
N
:
0=OFF, 1=lower threshold alarm, 2=higher threshold alarm.
9