- 69 -
Address Type
Holding Register description
AP ED RE AL
4000
to 4001
SW Lower alarm threshold as number of
counts
. Only if the chan-
nel is configured as counter (HD35EDH).
9
4002
to 4003
SW Higher alarm threshold as number of
counts
. Only if the
channel is configured as counter (HD35EDH).
9
4004
to 4005
SW
Lower alarm threshold expressed as value of the quantity asso-
ciated to the channel when the channel is configured as counter
(HD35EDH).
9
4006
to 4007
SW
Higher alarm threshold expressed as value of the quantity asso-
ciated to the channel when the channel is configured as counter
(HD35EDH).
9
General information
10000
to 10019
B
User code with ASCII codification.
Acceptable values are in the set {32,…,126}.
9
9
9
9
10020 W
Current
year
9
10021 W
Current
month
9
10022 W
Current
day
9
10023 W
Current
hour
9
10024 W
Current
minute
9
10025
W
Current second
9
10026 W
Measurement interval: 0=1s, 1=2s, 2=5s, 3=10s, 4=15s, 5=30s,
6=1min, 7=2min, 8=5min, 9=10min, 10=15min, 11=30min, 12=1h
9
10027 W
Logging/RF interval: 0=1s, 1=2s, 2=5s, 3=10s, 4=15s, 5=30s,
6=1min, 7=2min, 8=5min, 9=10min, 10=15min, 11=30min, 12=1h
9
9
10029 W
Network RF channel. By changing this register, all network de-
vices migrate to the new RF channel.
9
10030 W
Max number of RF transmissions for each command sent by AP
to a remote device.
9
10031 W
Packet Error Rate threshold in % (x10) for RF alarms genera-
tion (for ex. 500 means 50.0%)
9
10032 W
Temperature measurement unit: 0=°C, 1=°F
The setting is extended to all EDs except for mapped quanti-
ties in HD35EDH
9
10033 W
Atmospheric pressure measurement unit: see TAB
10.1.
The setting extends to all EDs except for mapped quantities in
HD35EDH
9
10034
W
Baud rate RS485: 0=9600, 1=19200, 3=38400 bit/s
9
10035 W
RS485 communication mode:
0=8N1, 1=8N2, 2=8E1, 3=8E2, 4=8O1, 5=8O2
9
10036 W
Password to be supplied to enable configuration change com-
mands. The reading provides the fixed value 32768.
9
10037 B
Device group with ASCII codification.
Acceptable values are in the set {32,…,126}.
9
9
9
9
10049 W
Differential pressure measurement unit for ranges r1, r2 and r3:
see TAB
10.1. The setting is extended to all EDs except for the
mapped quantities in HD35EDH
9
10050 W
Differential pressure measurement unit for range r4: see TAB
10.1. The setting is extended to all EDs except for the mapped
quantities in HD35EDH
9
10052 W
Setting of the quantities to be displayed in the automatic view-
ing cycle for models HD35EDLW… without keyboard. Set the
i-th bit (starting from LSB) to 1 if you wish to include the i-th
quantity in the viewing cycle.
Example
: if in the model measuring and calculating: 1=Temp.,
2=RH, 3=Td, 4=PVP, 5=Mix.Ratio, 6=AH, 7=Tw, the register is
set to 0000 0000 0010 0010, only the relative humidity (RH)
and the absolute humidity (AH) will be displayed alternatively.
9