- 70 -
Address Type
Holding Register description
AP ED RE AL
10053 W
Setting of the RF quantities (RSSI, PER%) to be displayed in the
automatic viewing cycle for models HD35EDLW… without key-
board. Set the i-th bit (starting from LSB) to 1 if you wish to
include the i-th quantity in the viewing cycle.
9
10054
W
Period, in hours, of CO
2
sensor auto calibration.
9
10055 W
Period, in hours, after which the first CO
2
auto calibration after
activation will occur.
9
10056 W
CO
2
reference value (in ppm) for auto calibration.
9
10057 W
CO
2
maximum acceptable variation (in ppm), with respect to
the reference value, for auto calibration.
9
10058 W
Relay #1 activation duration in seconds (1…54000 s) in case of
cyclical activation (
Coils – address 18 = 0
).
9
10059 W
Relay #1 deactivation duration in seconds (1…54000 s) in case
of cyclical activation (
Coils – address 18 = 0
).
9
10060 W
Number of relay #1 activations in case of cyclical activation
(
Coils – address 18 = 0
).
9
10061 W
Relay #2 activation duration in seconds (1…54000 s) in case of
cyclical activation
(Coils – address 21 = 0
).
9
10062 W
Relay #2 deactivation duration in seconds (1…54000 s) in case
of cyclical activation (
Coils – address 21 = 0
).
9
10063 W
Number of relay #2 activations in case of cyclical activation
(
Coils – address 21 = 0
).
9
20000
to 20011
B
User code with ASCII codification of measurement #1.
Available for models with more measurements of the same type.
9
20012
to 20023
B
User code with ASCII codification of measurement #2.
Available for models with more measurements of the same type.
9
20024
to 20035
B
User code with ASCII codification of measurement #3.
Available for models with more measurements of the same type.
9
20036
to 20047
B
User code with ASCII codification of measurement #4.
Available for models with more measurements of the same type.
9
20048
to 20059
B
User code with ASCII codification of measurement #5.
Available for models with more measurements of the same type.
9
20060
to 20071
B
User code with ASCII codification of measurement #6.
Available for models with more measurements of the same type.
9
20072
to 20083
B
User code with ASCII codification of measurement #7.
Available for models with more measurements of the same type.
9
20084
to 20095
B
User code with ASCII codification of measurement #8.
Available for models with more measurements of the same type.
9
20096
to20107
B
User code with ASCII codification of measurement #9.
Available for models with more measurements of the same type.
9
20108
to 20119
B
User code with ASCII codification of measurement #10.
Available for models with more measurements of the same type.
9
20120
to 20131
B
User code with ASCII codification of measurement #11.
Available for models with more measurements of the same type.
9
20132
to 20143
B
User code with ASCII codification of measurement #12.
Available for models with more measurements of the same type.
9
Warning
: the execution of MODBUS commands changing the parameters setting of a device
can take a certain time, due to the RF transmission between the device and the base unit. The
value of the flag PENDING_CONF (Discrete Inputs – address 2) is set to 1 during the execution
of a configuration change request. Only when the flag returns to 0 the request is considered as
concluded. The flag CMD_FAILURE (Coils – address 7) allows to check whether the request was
successful. It is recommended to check the status of the two flags before considering a device
configuration changed.