background image

 

HD33[L]M.GSM

 

-   11   - 

V1.10

 

10

 

SMS COMMANDS 

SMS messages containing commands can be sent by a mobile phone to the data logger. The 
SMS must be sent to the number of the SIM card inserted into the data logger. The following 
table lists the available commands: 

SMS commands 

Command 

Description 

RESET 

Reset of the device 

EMAIL-ON 

Activates periodic download of measurement data via e-mail 

EMAIL-OFF 

Deactivates periodic download of measurement data via e-mail 

EMAIL-PERIOD=

 period index

 

Set the transmission interval via e-mail, where 

period index

: 0->15 min, 1->30 

min, 2->1 hour, 3->2 hours, 4->4 hours, 5->8 hours, 6->12 hours, 7->24 hours, 

8->2 days, 9->4 days, 10->1 week 

EMAIL-FORMAT=

 format index

 

Set the format of the data sent via e-mail, where 

format index

1->log (format for database), 2->csv (format for Excel

®

), 3->log+csv 

EMAIL-DL-START 

Activates immediate data download by e-mail starting from the last 

measurement transmitted 

EMAIL-DL-FROM=

YYYY/MM/DD 

HH:MM:SS

 

Downloads data by e-mail starting from the specified date, where YYYY: year, 

MM: month, DD: day, HH: hour, MM: minutes, SS: seconds 

EMAIL-DL-INTERVAL=

YYYY/MM/DD 

HH:MM:SS - YYYY/MM/DD HH:MM:SS

 

Downloads by e-mail all data between the specified dates,  where YYYY: year, 

MM: month, DD: day, HH: hour, MM: minutes, SS: seconds 

EMAIL-ALARM-REPORT 

Transmits by e-mail a report containing the measurements that can generate 

alarms 

EMAIL-REPORT 

Transmits by e-mail a report containing the current measurements 

EMAIL-HELP 

Transmits an e-mail containing a list of all SMS commands 

FTP-ON 

Activates the periodic download of measurement data via FTP 

FTP-OFF 

Deactivates the periodic download of measurement data via FTP 

FTP-PERIOD=

 period index

 

Set the transmission interval via FTP, where 

period index

: 0->15 min, 1->30 min, 

2->1 hour, 3->2 hours, 4->4 hours, 5->8 hours, 6->12 hours, 7->24 hours, 

8->2 days, 9->4 days, 10->1 week 

FTP-FORMAT=

 format index

 

Set the format of the data sent via FTP, where 

format index

1->log (format for database), 2->csv (format for Excel

®

), 3->log+csv 

FTP-DL-START 

Activates immediate data download by FTP starting from the last 

measurement transmitted 

FTP-DL-FROM=

YYYY/MM/DD 

HH:MM:SS

 

Downloads data via FTP starting from the specified date, where YYYY: year, 

MM: month, DD: day, HH: hour, MM: minutes, SS: seconds 

FTP-DL-INTERVAL=

YYYY/MM/DD 

HH:MM:SS - YYYY/MM/DD HH:MM:SS

 

Downloads by FTP all data between the specified dates,  where YYYY: year, 

MM: month, DD: day, HH: hour, MM: minutes, SS: seconds 

FTP-ALARM-REPORT 

Transmits by FTP a report containing the measurements that can generate 

alarms 

FTP-REPORT 

Transmits by FTP a report containing the current measurements 

FTP-HELP 

Transmits by FTP a file containing a list of all SMS commands 

SMS-ALARM-ON 

Activates the transmission of alarm SMS for the overrun of the measurement 

thresholds (if the device is selected for sending alarm SMS)  

SMS-ALARM-OFF 

Deactivates the transmission of alarm SMS for the overrun of the measurement 

thresholds for the selected devices 

EMAIL-ALARM-ON 

Activates the transmission of e-mail measurements alarms (if the device is 

selected for sending alarm e-mail)  

EMAIL-ALARM-OFF 

Deactivates the transmission of e-mail alarms for measurement alarms 

SMS-ALARM-REPORT 

Indicates whether the measurements are in alarm. Only the selected 

measurements are taken into consideration for SMS alarms 

Summary of Contents for HD33[L]M.GSM

Page 1: ...Operating manual GSM Data Logger HD33 L M GSM Keep for future reference www deltaohm com English Companies Brands of GHM...

Page 2: ...TECHNICAL CHARACTERISTICS 5 4 MEASURING PROBES 7 5 SIM CARD 8 6 INSTALLATION 9 7 POWER SUPPLY 9 8 USB CONNECTION 10 9 HD35AP S SOFTWARE 10 10 SMS COMMANDS 11 11 GPRS TCP IP CONNECTION 13 12 STORAGE OF...

Page 3: ...o GSM GPRS transmission the user will not have to remove the data logger from its position or reach the place where the data logger is installed to download the data measured with the PC the instrumen...

Page 4: ...or LED red blinking indicates that the instrument is powered blinks green to signal the GSM activity 4 Custom LCD display The cyclic automatic scrolling of the measurements can be set with the HD35AP...

Page 5: ...Weight 1 kg approx including shield and fixing clamping Housing Dimensions 122 x 120 x 56 mm excluding external antenna Material Polycarbonate PC Protection degree IP 67 with protective cap on the US...

Page 6: ...tes to an hourly value For the other characteristics please refer to the data sheet of the chosen rain gauge A measurement compensation curve as a function of the rainfall rate can be configured Wind...

Page 7: ...lable Solar radiation The pyranometers LP PYRA 02 LP PYRA 03 LP PYRA 10 LP SILICON PYRA 04 etc with mV output signal can be connected Wind speed and direction For the measurement of wind speed and dir...

Page 8: ...t the SIM tray back in place and push the metal block in the direction of the arrow LOCK 6 Close again the housing by fixing the 4 front screws Through the HD35AP S software set the necessary informat...

Page 9: ...th direct voltage from 7 to 30 Vdc and can be powered by mains through the power supply unit HD32MT SWD or by a solar panel through the power supply unit HD32WSF S12 that includes a 12 Vdc 7 2 Ah batt...

Page 10: ...it is not powered by the PC USB port When the data logger is not connected to the PC replace the mini USB connector protective cap to ensure the watertight integrity of the instrument 9 HD35AP S SOFTW...

Page 11: ...of measurement data via FTP FTP OFF Deactivates the periodic download of measurement data via FTP FTP PERIOD period index Set the transmission interval via FTP where period index 0 15 min 1 30 min 2 1...

Page 12: ...date where YYYY year MM month DD day HH hour MM minutes SS seconds HTTP DL INTERVAL YYYY MM DD HH MM SS YYYY MM DD HH MM SS Uploads on the HTTP server all data between the specified dates where YYYY y...

Page 13: ...he Modem Router 4 Disconnect the data logger from the USB port 5 In the HD35AP S software select Tools Type of connection select the TCP server option and set the number of the port opened in the Mode...

Page 14: ...safety technical conditions The regular functioning and operational safety of these instruments can be ensured only if all normal safety measures as well as the specific measures described in this man...

Page 15: ...K sensor temperature probe Measuring range 40 105 C Probe stem AISI 304 14 mm length 150 mm Cable length 2 5 or 10 m standard 4 pole M12 female connector HD9007A 1 12 ring protection against solar rad...

Page 16: ...ion 0 2 mm 0 1 or 0 5 mm on request with order Normally closed output contact Power supply 12 Vdc or 24 Vdc 10 absorbed power 50 W HD2016 Weighing rain gauge area 400 cm2 3000 cc collecting reservoir...

Page 17: ...itions 40 60 C 0 100 RH Rod mounting Dimensions 210 x 120 mm HD54 9K Transverse mast kit including transverse mast 40 mm and L 1500 mm two extension bars 40 mm and accessories ACCESSORIES HD35AP CFR21...

Page 18: ...n be fixed on a flat base with screws or to the ground with pegs Foldable legs for the transport HD2005 20 1 Tripod kit with adjustable legs for installing environmental sensors pyranometers temperatu...

Page 19: ......

Page 20: ...third parties is excluded from the guarantee The instrument shall be returned FREE OF SHIPMENT CHARGES to your dealer The jurisdiction of Padua applies in any dispute The electrical and electronic eq...

Page 21: ...e result of the constant development of the product This may produce some differences between the information written in this manual and the instrument you have purchased We cannot completely exclude...

Page 22: ...GHM GROUP Delta OHM Delta Ohm S r l a socio unico Via Marconi 5 35030 Caselle di Selvazzano Padova ITALY Phone 39 049 8977150 Fax 39 049 635596 www deltaohm com info deltaohm com V1 10 10 10 2018...

Reviews: