HD45 / HD46
- 12 -
V2.4
4. OPERATION MODE
After installing and connecting the transmitter as shown in section INSTALLATION
AND CONNECTION, supply the instrument with the correct voltage.
A wrong power
supply may cause permanent damage to the instrument.
“POWER” LED activation indicates that the instrument is being powered.
In models provided with a display, the indication of the transmitter model and
firmware version are displayed and, after a few seconds, measures are shown. The
instruments display all measured values simultaneously.
Temperature – Humidity
Temperature
Temperature – Humidity
and
CO
2
and CO
2
HD45
17…
HD46
17B… HD45
7B… HD46
17…
Fig. 4.A: Viewing measures in models with a display
Models are preset to display temperature in °C and relative humidity in %. You can
setup instruments to display temperature in °F and humidity as dewpoint.
Td = Dewpoint
T = T ambient – Td
Fig. 4.B: Viewing humidity as dewpoint
The instrument requires about 15 minutes to ensure stable measures and indicated
accuracy.
In models provided with a keyboard, you can turn on the display backlight by pressing
any key. Backlight turns off after 30 minutes of keyboard inactivity.
The instruments are factory preset to be immediately operative. The user can easily
customize the configuration of the instrument by connecting it to a PC or by means of
the front keyboard, for instruments supplied with a keyboard. For details on
configuration, see section “CONFIGURATION”.
The instruments are preset to operate in still air (< 0.25 m/s). To operate in circulating
air (e.g. in a climatic room), the operating mode of the instruments must be changed
(see the commands Cu0 and Cu1 on pag. 39).