Watertight
Connector
Flexible
Sensor
Cord Conduit
257mm (10.13")
Control Box
305mm (12")
Stainless Steel
Cover Plate
102mm (4")
355mm
(14”) max.
Fig. 8
Product supplied
as shown by solid
lines. All items
shown by dotted
lines supplied by
others.
Sensor
Page 4
212294 Rev.
B
FOR RECESS MOUNT HOUSING: CONTROL BOXES #1 & 8
STEP 3. CONNECT WATER SUPPLY
Install sink and connect drainage to rough in. See
applicable Fig. 6
or Fig. 7. Please note that the connec-
tion and fittings are supplied by the installer to connect
1/2” nominal sweat at the box outlet and 3/8” compression
at the spout. Connect water supply through to spout.
Assure supply lines are completely flushed and free of
debris.
STEP 4. FLUSH SYSTEM/SET TEMPERATURE
Remove coverplate from control box. Open screwdriver
stop(s) to flush installation for
1 minute minimum.
4A
Run water for a sufficient time so the hot and cold
water supplies are as hot and cold as they will get.
4B
Place a thermometer in a plastic container and hold
in the water stream. Record the temperature reading
and note position of temperature control, and lock at
desired setting.
4C
Thermostatic Mixing Valve
(Fig. 7) To adjust the
mixed outlet temperature of the valve, remove the
cap to gain access to the adjusting spindle. The
spindle should be rotated towards the “C” side to
reduce the temperature and towards the “H” side to
increase the temperature - until the desired set point
is reached (refer to Fig. 9).
Periodic Inspection/Maintenance
- We recommend
that this valve is checked at least once per year to
ensure its continued function. For installations with
poor or unknown water quality, or other adverse
supply conditions, it may be necessary to check the
valve at more frequent intervals. The temperature should be checked at the same outlet
as was used for commissioning in the first instance. If the temperature is more than 3°F
from the commissioning in temperature, refer to the included Cash Acme Maintenance
and Installation Guide.
4D
Close stop(s).
STEP 5. CONNECT ELECTRICAL SUPPLY, SOLENOID VALVE AND SENSOR
Remove plastic threaded spacer nipple and install solenoid valve with body arrow in the
direction of water flow. See Fig. 10. Feed sensor wire from spout into control box and then
connect to the driver board. Connect red solenoid wire from the driver board to “+” marked
solenoid terminal on solenoid valve, black solenoid wire to other solenoid terminal.
BATTERY VERSION
Install four “Alkaline C” batteries provided into the battery holder. Connect
battery clip from the driver board to battery pack. Ensure snap does not touch any conductive
metal surface. Two beeps indicate power is ready for use. Use caution not to damage wires or
components on electronic driver board. Secure cover using screws. Do not use 9V battery.
HARDWIRE VERSION
Install CSA and/or UL approved Class 2 transformer or equivalent in a
convenient location or in a pipe chase.
(Do NOT install the transformer inside the control
box.)
With the power off, bring the 24 VAC supply wires into the box. Connect the 24 VAC supply to
the 060683A conversion kit. Connect the battery snap of the hardwire converter to the driver
board battery clip. Ensure snap does not touch any conductive metal surface. Turn on power
supply for the transformer. Secure cover using screws. Do not remove battery snap from
hardwire converter by using a flat screwdriver, damage may result.
STEP 6. SERVICES
Open screwdriver stop(s). Flush line. Install aerator.
Cover
Fig. 10
Valve
Spacer
(Replace
with
Solenoid
Valve &
Washers
after system
is flushed)
Solenoid Valve
(INSTALL:
replacing
SPACER after
system is
flushed.)
SOLENOID
may be
ROTATED to
ALLOW for installation
of COVER ASSEMBLY.
INSTALLATION AND SET UP INSTRUCTIONS
w w w . s p e c s e l e c t . c o m
Connection
and Fittings
by Installer
Fig. 9
Towards
“H” side to
increase
temperature
Towards
“C” side
to reduce
temperature