English-
11
Pr.
Explanation
Settings
Factory
Setting
NOTE
00.01 Rated
Current
Display of the AC
motor drive
Read-only
#.#
00.02 Parameter
Reset
0: Parameter can be read/written
1: All parameters are read only
6: Clear PLC program
(NOT for VFD*E*C
models)
9: All parameters are reset to factory settings
(50Hz, 230V/400V or 220V/380V depends
on Pr.00.12)
10: All parameters are reset to factory
settings (60Hz, 220V/440V)
0
a
00.03
Start-up Display
Selection
0: Display the frequency command value
(Fxxx)
1: Display the actual output frequency (Hxxx)
2: Display the content of user-defined unit
(Uxxx)
3: Multifunction display, see Pr.00.04
4: FWD/REV command
5: PLCx (PLC selections: PLC0/PLC1/PLC2)
(NOT for VFD*E*C models)
0
a
00.04
Content of Multi-
function Display
0: Display the content of user-defined unit
(Uxxx)
1: Display the counter value (c)
2: Display PLC D1043 value (C)
(NOT for
VFD*E*C models)
3: Display DC-BUS voltage (u)
4: Display output voltage (E)
5: Display PID analog feedback signal value
(b) (%)
6: Output power factor angle (n)
7: Display output power (P)
8: Display the estimated value of torque as it
relates to current (t)
9: Display AVI (I) (V)
10: Display ACI / AVI2 (i) (mA/V)
11: Display the temperature of IGBT (h) (
°
C)
12: Display AVI3/ACI2 level (I.)
13: Display AVI4/ACI3 level (i.)
14: Display PG speed in RPM (G)
15: Display motor number (M)
0
a
00.05
User-Defined
Coefficient K
0. 1 to 160.0
1.0
00.06 Power
Board
Software Version
Read-only
#.##
00.07 Control
Board
Software Version
Read-only
#.##
00.08
Password Input
0 to 9999
0
00.09
Password Set
0 to 9999
0
00.10 Control
Method
0: V/f Control
1: Vector Control
0
00.11 Reserved