English-
9
The Specification for the Control Terminals
RS-485 port
10V
MI1 MI2 MI3 MI4 MI5 MI6
DCM
24V
DCM
ACM
AVI ACI
AFM MCM MO1
RA
RB
RC
The position of the control terminals
Terminals 2
Terminals 1
Frame
Control Terminals
Torque
Wire
Terminals 1
5 kgf-cm (4.4 in-lbf)
12-24 AWG (3.3-0.2mm
2
)
A, B, C
Terminals 2
2 kgf-cm (2 in-lbf)
16-24 AWG (1.3-0.2mm
2
)
NOTE
Frame A:
VFD002E11A/21A/23A, VFD004E11A/21A/23A/43A, VFD007E21A/23A/43A,
VFD015E23A/43A, VFD002E11C/21C/23C, VFD004E11C/21C/23C/43C,
VFD007E21C/23C/43C, VFD015E23C/43C, VFD002E11T/21T/23T,
VFD004E11T/21T/23T/43T, VFD007E21T/23T/43T, VFD015E23T/43T,
VFD002E11P/21P/23P, VFD004E11P/21P/23P/43P, VFD007E21P/23P/43P,
VFD015E23P/43P
Frame B:
VFD007E11A, VFD015E21A, VFD022E21A/23A/43A, VFD037E23A/43A
Frame C:
VFD055E23A/43A, VFD075E23A/43A, VFD110E43A
Control Terminals Explanations
Terminal
Symbol
Terminal Function
Factory Settings (NPN mode)
ON: Connect to DCM
MI1 Forward-Stop
command
ON:
Run in MI1 direction
OFF:
Stop acc. to Stop Method
MI2 Reverse-Stop
command
ON:
Run in MI2 direction
OFF:
Stop acc. to Stop Method
MI3 Multi-function
Input
3
MI4 Multi-function
Input
4
MI5 Multi-function
Input
5
MI6 Multi-function
Input
6
Refer to Pr.04.05 to Pr.04.08 for programming the
Multi-function Inputs.
ON: the activation current is 5.5mA .
OFF: leakage current tolerance is 10
μ
A.
+24V
DC Voltage Source
+24VDC, 20mA used for PNP mode.
RA
Multi-function Relay output
(N.O.) a
RB
Multi-function Relay output
(N.C.) b
RC
Multi-function Relay common
Resistive Load:
5A(N.O.)/3A(N.C.) 240VAC
5A(N.O.)/3A(N.C.) 24VDC
Inductive Load:
1.5A(N.O.)/0.5A(N.C.) 240VAC
1.5A(N.O.)/0.5A(N.C.) 24VDC
Refer to Pr.03.00 for programming
DCM Digital
Signal
Common
Common for digital inputs and used for NPN
mode.